# Temperature Sensor - Quick Reference SSO **Device Type:** Analog Input - Sensor **Signal:** Thermistor (10K) / 0-10VDC / 4-20mA **Power:** Unpowered (thermistor) / 24VAC-VDC (transmitter) **Version:** 1.0 | **Date:** Dec 2025 --- ## DEVICE OVERVIEW **Common Models:** - Johnson Controls TE-6000, Honeywell T7350, Siemens QAA, Belimo 22RT, BAPI BA/10K **Used For:** Space temperature, duct air temp, immersion (water/glycol), outdoor air sensing **Wire Type:** 18AWG minimum, 16AWG recommended, shielded if >50ft **Environment:** Space 32-120°F | Duct -40-200°F | Immersion -40-250°F --- ## SAFETY - PPE REQUIRED - ☑ Safety glasses (ANSI Z87.1) - ☑ Cut-resistant gloves (sheet metal) - ☑ Hard hat (mechanical rooms/rooftops) - ☑ Dust mask (drilling ducts) - ☑ Fall protection (if >6 feet height) ### HAZARDS - ⚠ Sharp edges - Sheet metal ductwork - ⚠ Hot/cold surfaces - Ducts near coils, pipes - ⚠ Falls - Ladder work, rooftop access - ⚠ Rotating equipment - Air handler fans (LOTO required) ### LOCKOUT/TAGOUT - [ ] **Required for duct sensors:** Lock out air handler before drilling duct - [ ] Notify building operator - [ ] Lock breaker with personal lock - [ ] Test that fan won't start - [ ] Remove lock only after work complete --- ## INSTALLATION CHECKLIST ### TOOLS NEEDED - Drill + bits (1/16"-1/2") - Hole saw (3/4"-1" for duct) - Wire strippers (18-16 AWG) - Multimeter (DMM) - Level, tape measure - Deburring tool - Duct sealant (high-temp) - Label maker ### PRE-INSTALL - [ ] Location per blueprints verified - [ ] Space sensor: Away from sun, exterior walls, diffusers (6ft), doors (3ft) - [ ] Duct sensor: Straight section (3× duct diameter from elbows) - [ ] Outside sensor: North wall, away from exhaust (10ft) - [ ] Correct sensor type for controller input (thermistor vs transmitter) ### INSTALL STEPS - SPACE SENSOR 1. **Mount:** 48-60" above floor, interior wall, use level 2. **Route Wire:** Through wall/conduit, 12" service loop 3. **Terminate (Thermistor 2-wire):** - Wire 1 (Red): Terminal 1 - Wire 2 (Black): Terminal 2 - Polarity doesn't matter for thermistor 4. **Terminate (Transmitter 3-wire):** - Red: +24VAC/VDC - Black: Common/Ground - White/Green: Signal output 5. **Label:** "RM-[#]-TEMP" both ends 6. **Install cover** and verify level ### INSTALL STEPS - DUCT SENSOR 1. **LOCKOUT air handler** before starting 2. **Mark location:** Straight duct, avoid seams/ribs 3. **Drill penetration:** Pilot hole → Hole saw → Deburr edges 4. **Insert probe:** 1/3 duct width (spot) or full width (averaging) 5. **Secure flange:** Sheet metal screws, tight but not distorted 6. **Seal penetration:** High-temp duct sealant, no air leaks 7. **Terminate wiring:** Per sensor type (above) 8. **Restore system:** Remove lockout, verify fan starts ### INSTALL STEPS - IMMERSION SENSOR 1. **Verify thermowell** present in pipe 2. **Apply thermal compound** to probe tip 3. **Insert probe** fully into thermowell 4. **Tighten compression fitting:** Hand tight + 1/4 turn with wrench 5. **Terminate wiring** and support with cable ties ### POST-INSTALL - [ ] Device mounted securely and level - [ ] All wires tight (7-9 in-lbs torque) - [ ] Labels applied both ends - [ ] Duct penetrations sealed (no leaks) - [ ] Work area cleaned - [ ] Photos taken --- ## EXPECTED READINGS ### PRE-POWER (Power OFF) **THERMISTOR (2-wire, unpowered):** - **Resistance at 70°F:** 9,500 - 10,500 ohms (10K Type II/III) - **At 60°F:** ~12,500 ohms - **At 80°F:** ~8,000 ohms - **If infinity:** Open circuit - failed sensor or broken wire - **If near zero:** Short circuit **TRANSMITTER (3-wire):** - **Continuity:** Each wire <5 ohms end-to-end **ISOLATION:** >10K ohms to ground (all types) ### POWER-UP **THERMISTOR:** - Controller provides excitation (~5VDC) - Controller converts resistance to temperature **TRANSMITTER:** - **Supply Voltage:** 24VAC/VDC ±10% (21.6-26.4V acceptable) - **Output at 70°F (0-10V, 0-100°F range):** ~7.0V - **Output at 70°F (4-20mA, 0-100°F range):** ~15.2mA ### ACCEPTABLE RANGE - SPACE TEMP - ✓ Reading: 68-72°F at room temp (±2°F initially acceptable) - ✓ Response time: 30-90 seconds to stabilize - ✓ Controller shows reading (no faults) - ✓ Graphics display live value ### TYPICAL READINGS - DUCT - **Supply Air Cooling:** 50-60°F - **Supply Air Heating:** 90-120°F - **Return Air:** 68-76°F - **Outside Air:** Matches local weather (±5°F) ### TYPICAL READINGS - IMMERSION - **Chilled Water Supply:** 42-48°F - **Chilled Water Return:** 52-58°F - **Hot Water Supply:** 140-180°F - **Condenser Water:** 70-95°F --- ## PROOF OUT TESTS ### TEST 1: Response Test - **Do:** Place hand over space sensor (or heat duct sensor with breath) - **Expect:** Reading increases 3-8°F within 30-60 seconds - **Pass If:** Reading changes and returns to baseline when removed ### TEST 2: Accuracy Check - **Do:** Compare to calibrated reference thermometer (within 6") - **Expect:** Reading within ±2°F of reference - **Pass If:** Within tolerance after 5 min stabilization ### TEST 3: Stability Check - **Do:** Monitor reading for 5 minutes - **Expect:** Stable reading (±1°F variation max) - **Pass If:** No erratic jumping or oscillation ### TEST 4: Controller Integration - [ ] Device appears in controller point list - [ ] Reading displays correctly (no faults) - [ ] Graphics show live data updating - [ ] Control system responds to sensor (heating/cooling calls) --- ## TROUBLESHOOTING ### NO POWER / NO READING / FAULT 1. **Thermistor:** Measure resistance at sensor: Should be ~10K at 70°F - If infinity: Replace sensor (open circuit) - If near zero: Replace sensor (short circuit) 2. **Transmitter:** Check supply voltage at sensor: 24V ±10% 3. Test continuity end-to-end: <5 ohms 4. Check all terminal connections tight 5. Verify polarity correct (transmitters only) 6. **If still dead:** Replace device ### READING TOO HIGH OR LOW (Offset) 1. Compare to calibrated reference thermometer 2. **Space sensor:** Check for influences: - Direct sunlight, heat sources, cold surfaces - Too close to diffuser (<6ft) or exterior wall 3. **Duct sensor:** Verify insertion depth (1/3 width typical) 4. **Immersion sensor:** Verify probe fully inserted in thermowell 5. Wait 30 min for stabilization 6. **If consistently off by same amount:** Apply controller calibration offset 7. **If off by >5°F:** Relocate or replace sensor ### ERRATIC / JUMPING READINGS 1. Check all terminal connections tight (wiggle test) 2. Inspect wiring for damage, pinching 3. **Check for EMI/RFI interference:** - Wire running parallel to power cables? - Near motors, VFDs, transformers? 4. Verify shielded cable used if required (>50ft runs) 5. Test at sensor AND at controller (same reading?) 6. Look for moisture in connections 7. **If wiring OK:** Replace sensor ### SLOW RESPONSE 1. Normal: 30-90 seconds for most sensors 2. **Duct sensor:** May be outside airstream - check depth 3. Check for buildup on sensor element 4. **If >2 minutes consistently:** Clean or replace --- ## ESCALATION - COMPLETE BEFORE CALLING ### PRE-ESCALATION CHECKLIST - [ ] Verified supply voltage at sensor (transmitters: 24V ±10%) - [ ] Tested sensor resistance (thermistors: ~10K at 70°F) - [ ] Verified all wire connections tight and correct - [ ] Tested continuity end-to-end (<5 ohms) - [ ] Compared to calibrated reference thermometer - [ ] Checked for environmental influences - [ ] Verified sensor type matches controller input config - [ ] Documented all readings with multimeter - [ ] Taken photos of installation and wiring - [ ] Reviewed sensor installation manual ### PROVIDE THIS INFO - **Device:** [Mfg / Model / Location] - **Sensor Type:** Thermistor / 0-10V / 4-20mA - **Measured Resistance:** _____ ohms (thermistors) - **Supply Voltage:** _____ V (transmitters) - **Output Signal:** _____ V or mA - **Controller Reading:** _____ °F - **Reference Reading:** _____ °F - **Error:** _____ °F (sensor - reference) - **Environment:** Temp ____ / Humidity ____ / Airflow ____ - **Steps Taken:** [List troubleshooting completed] - **Photos:** Attached to Service Fusion ticket ### CONTACTS - **Field Specialist:** [Phone] - **Programmer:** [Phone] (if calibration offset needed) - **Project Manager:** [Phone] (if design/location issue) - **Dispatch:** [Phone] (parts/resources) --- ## CALIBRATION **When Required:** All sensors verified during commissioning, annually for critical apps **Quick Steps:** 1. **Stabilize:** Wait 15-30 min (space), 30 min (duct with system running) 2. **Position reference:** Within 6" of sensor, same height/location 3. **Wait:** 2-3 min for reference to stabilize 4. **Compare:** - Sensor reading: ______°F - Reference reading: ______°F - Error: ______ °F 5. **Acceptable:** ±2°F for most BAS, ±1°F for tight tolerance apps **If Outside Tolerance:** - **Option A (Preferred):** Apply controller calibration offset - Access controller config for this input - Enter offset value (+ if sensor reads low, - if reads high) - Verify reading now matches reference - Document offset in Service Fusion - **Option B:** Adjust sensor (if has calibration pot) - Remove cover, locate adjustment screw - Adjust while monitoring reading - Re-verify with reference - **If Cannot Calibrate:** Replace sensor **Document:** Tech name, date, reference ID & cal date, before/after readings --- ## COMMON ISSUES & TIPS ✓ **Space sensors reading high:** Check if in direct sun or near heat source ✓ **Duct sensors inaccurate:** Verify insertion depth (1/3 width for spot sensing) ✓ **Outdoor sensors erratic:** Ensure north-facing, away from exhaust/relief dampers ✓ **Immersion sensors slow:** Normal - thermal mass requires 15-20 min to respond ✓ **All sensors offset same amount:** Apply controller calibration offset, don't replace ✓ **Shielded cable:** Ground shield at controller end ONLY (not both ends) ✓ **10K Type II vs Type III:** Most controllers auto-detect, but verify in config --- **Document ID:** SSO-TEMP-001 **Revision:** 1.0 **Next Review:** Dec 2026
