# Temperature Sensor - Quick Reference SSO
2
3
**Device Type:** Analog Input - Sensor
4
**Signal:** Thermistor (10K) / 0-10VDC / 4-20mA
5
**Power:** Unpowered (thermistor) / 24VAC-VDC (transmitter)
6
**Version:** 1.0 | **Date:** Dec 2025
7
8
---
9
10
## DEVICE OVERVIEW
11
12
**Common Models:**
13
- Johnson Controls TE-6000, Honeywell T7350, Siemens QAA, Belimo 22RT, BAPI BA/10K
14
15
**Used For:**
16
Space temperature, duct air temp, immersion (water/glycol), outdoor air sensing
17
18
**Wire Type:** 18AWG minimum, 16AWG recommended, shielded if >50ft
19
**Environment:** Space 32-120°F | Duct -40-200°F | Immersion -40-250°F
20
21
---
22
23
## SAFETY - PPE REQUIRED
24
25
- ☑ Safety glasses (ANSI Z87.1)
26
- ☑ Cut-resistant gloves (sheet metal)
27
- ☑ Hard hat (mechanical rooms/rooftops)
28
- ☑ Dust mask (drilling ducts)
29
- ☑ Fall protection (if >6 feet height)
30
31
### HAZARDS
32
- ⚠ Sharp edges - Sheet metal ductwork
33
- ⚠ Hot/cold surfaces - Ducts near coils, pipes
34
- ⚠ Falls - Ladder work, rooftop access
35
- ⚠ Rotating equipment - Air handler fans (LOTO required)
36
37
### LOCKOUT/TAGOUT
38
- [ ] **Required for duct sensors:** Lock out air handler before drilling duct
39
- [ ] Notify building operator
40
- [ ] Lock breaker with personal lock
41
- [ ] Test that fan won't start
42
- [ ] Remove lock only after work complete
43
44
---
45
46
## INSTALLATION CHECKLIST
47
48
### TOOLS NEEDED
49
- Drill + bits (1/16"-1/2")
50
- Hole saw (3/4"-1" for duct)
51
- Wire strippers (18-16 AWG)
52
- Multimeter (DMM)
53
- Level, tape measure
54
- Deburring tool
55
- Duct sealant (high-temp)
56
- Label maker
57
58
### PRE-INSTALL
59
- [ ] Location per blueprints verified
60
- [ ] Space sensor: Away from sun, exterior walls, diffusers (6ft), doors (3ft)
61
- [ ] Duct sensor: Straight section (3× duct diameter from elbows)
62
- [ ] Outside sensor: North wall, away from exhaust (10ft)
63
- [ ] Correct sensor type for controller input (thermistor vs transmitter)
64
65
### INSTALL STEPS - SPACE SENSOR
66
1. **Mount:** 48-60" above floor, interior wall, use level
67
2. **Route Wire:** Through wall/conduit, 12" service loop
68
3. **Terminate (Thermistor 2-wire):**
69
- Wire 1 (Red): Terminal 1
70
- Wire 2 (Black): Terminal 2
71
- Polarity doesn't matter for thermistor
72
4. **Terminate (Transmitter 3-wire):**
73
- Red: +24VAC/VDC
74
- Black: Common/Ground
75
- White/Green: Signal output
76
5. **Label:** "RM-[#]-TEMP" both ends
77
6. **Install cover** and verify level
78
79
### INSTALL STEPS - DUCT SENSOR
80
1. **LOCKOUT air handler** before starting
81
2. **Mark location:** Straight duct, avoid seams/ribs
82
3. **Drill penetration:** Pilot hole → Hole saw → Deburr edges
83
4. **Insert probe:** 1/3 duct width (spot) or full width (averaging)
84
5. **Secure flange:** Sheet metal screws, tight but not distorted
85
6. **Seal penetration:** High-temp duct sealant, no air leaks
86
7. **Terminate wiring:** Per sensor type (above)
87
8. **Restore system:** Remove lockout, verify fan starts
88
89
### INSTALL STEPS - IMMERSION SENSOR
90
1. **Verify thermowell** present in pipe
91
2. **Apply thermal compound** to probe tip
92
3. **Insert probe** fully into thermowell
93
4. **Tighten compression fitting:** Hand tight + 1/4 turn with wrench
94
5. **Terminate wiring** and support with cable ties
95
96
### POST-INSTALL
97
- [ ] Device mounted securely and level
98
- [ ] All wires tight (7-9 in-lbs torque)
99
- [ ] Labels applied both ends
100
- [ ] Duct penetrations sealed (no leaks)
101
- [ ] Work area cleaned
102
- [ ] Photos taken
103
104
---
105
106
## EXPECTED READINGS
107
108
### PRE-POWER (Power OFF)
109
110
**THERMISTOR (2-wire, unpowered):**
111
- **Resistance at 70°F:** 9,500 - 10,500 ohms (10K Type II/III)
112
- **At 60°F:** ~12,500 ohms
113
- **At 80°F:** ~8,000 ohms
114
- **If infinity:** Open circuit - failed sensor or broken wire
115
- **If near zero:** Short circuit
116
117
**TRANSMITTER (3-wire):**
118
- **Continuity:** Each wire <5 ohms end-to-end
119
120
**ISOLATION:** >10K ohms to ground (all types)
121
122
### POWER-UP
123
124
**THERMISTOR:**
125
- Controller provides excitation (~5VDC)
126
- Controller converts resistance to temperature
127
128
**TRANSMITTER:**
129
- **Supply Voltage:** 24VAC/VDC ±10% (21.6-26.4V acceptable)
130
- **Output at 70°F (0-10V, 0-100°F range):** ~7.0V
131
- **Output at 70°F (4-20mA, 0-100°F range):** ~15.2mA
132
133
### ACCEPTABLE RANGE - SPACE TEMP
134
- ✓ Reading: 68-72°F at room temp (±2°F initially acceptable)
135
- ✓ Response time: 30-90 seconds to stabilize
136
- ✓ Controller shows reading (no faults)
137
- ✓ Graphics display live value
138
139
### TYPICAL READINGS - DUCT
140
- **Supply Air Cooling:** 50-60°F
141
- **Supply Air Heating:** 90-120°F
142
- **Return Air:** 68-76°F
143
- **Outside Air:** Matches local weather (±5°F)
144
145
### TYPICAL READINGS - IMMERSION
146
- **Chilled Water Supply:** 42-48°F
147
- **Chilled Water Return:** 52-58°F
148
- **Hot Water Supply:** 140-180°F
149
- **Condenser Water:** 70-95°F
150
151
---
152
153
## PROOF OUT TESTS
154
155
### TEST 1: Response Test
156
- **Do:** Place hand over space sensor (or heat duct sensor with breath)
157
- **Expect:** Reading increases 3-8°F within 30-60 seconds
158
- **Pass If:** Reading changes and returns to baseline when removed
159
160
### TEST 2: Accuracy Check
161
- **Do:** Compare to calibrated reference thermometer (within 6")
162
- **Expect:** Reading within ±2°F of reference
163
- **Pass If:** Within tolerance after 5 min stabilization
164
165
### TEST 3: Stability Check
166
- **Do:** Monitor reading for 5 minutes
167
- **Expect:** Stable reading (±1°F variation max)
168
- **Pass If:** No erratic jumping or oscillation
169
170
### TEST 4: Controller Integration
171
- [ ] Device appears in controller point list
172
- [ ] Reading displays correctly (no faults)
173
- [ ] Graphics show live data updating
174
- [ ] Control system responds to sensor (heating/cooling calls)
175
176
---
177
178
## TROUBLESHOOTING
179
180
### NO POWER / NO READING / FAULT
181
1. **Thermistor:** Measure resistance at sensor: Should be ~10K at 70°F
182
- If infinity: Replace sensor (open circuit)
183
- If near zero: Replace sensor (short circuit)
184
2. **Transmitter:** Check supply voltage at sensor: 24V ±10%
185
3. Test continuity end-to-end: <5 ohms
186
4. Check all terminal connections tight
187
5. Verify polarity correct (transmitters only)
188
6. **If still dead:** Replace device
189
190
### READING TOO HIGH OR LOW (Offset)
191
1. Compare to calibrated reference thermometer
192
2. **Space sensor:** Check for influences:
193
- Direct sunlight, heat sources, cold surfaces
194
- Too close to diffuser (<6ft) or exterior wall
195
3. **Duct sensor:** Verify insertion depth (1/3 width typical)
196
4. **Immersion sensor:** Verify probe fully inserted in thermowell
197
5. Wait 30 min for stabilization
198
6. **If consistently off by same amount:** Apply controller calibration offset
199
7. **If off by >5°F:** Relocate or replace sensor
200
201
### ERRATIC / JUMPING READINGS
202
1. Check all terminal connections tight (wiggle test)
203
2. Inspect wiring for damage, pinching
204
3. **Check for EMI/RFI interference:**
205
- Wire running parallel to power cables?
206
- Near motors, VFDs, transformers?
207
4. Verify shielded cable used if required (>50ft runs)
208
5. Test at sensor AND at controller (same reading?)
209
6. Look for moisture in connections
210
7. **If wiring OK:** Replace sensor
211
212
### SLOW RESPONSE
213
1. Normal: 30-90 seconds for most sensors
214
2. **Duct sensor:** May be outside airstream - check depth
215
3. Check for buildup on sensor element
216
4. **If >2 minutes consistently:** Clean or replace
217
218
---
219
220
## ESCALATION - COMPLETE BEFORE CALLING
221
222
### PRE-ESCALATION CHECKLIST
223
- [ ] Verified supply voltage at sensor (transmitters: 24V ±10%)
224
- [ ] Tested sensor resistance (thermistors: ~10K at 70°F)
225
- [ ] Verified all wire connections tight and correct
226
- [ ] Tested continuity end-to-end (<5 ohms)
227
- [ ] Compared to calibrated reference thermometer
228
- [ ] Checked for environmental influences
229
- [ ] Verified sensor type matches controller input config
230
- [ ] Documented all readings with multimeter
231
- [ ] Taken photos of installation and wiring
232
- [ ] Reviewed sensor installation manual
233
234
### PROVIDE THIS INFO
235
- **Device:** [Mfg / Model / Location]
236
- **Sensor Type:** Thermistor / 0-10V / 4-20mA
237
- **Measured Resistance:** _____ ohms (thermistors)
238
- **Supply Voltage:** _____ V (transmitters)
239
- **Output Signal:** _____ V or mA
240
- **Controller Reading:** _____ °F
241
- **Reference Reading:** _____ °F
242
- **Error:** _____ °F (sensor - reference)
243
- **Environment:** Temp ____ / Humidity ____ / Airflow ____
244
- **Steps Taken:** [List troubleshooting completed]
245
- **Photos:** Attached to Service Fusion ticket
246
247
### CONTACTS
248
- **Field Specialist:** [Phone]
249
- **Programmer:** [Phone] (if calibration offset needed)
250
- **Project Manager:** [Phone] (if design/location issue)
251
- **Dispatch:** [Phone] (parts/resources)
252
253
---
254
255
## CALIBRATION
256
257
**When Required:** All sensors verified during commissioning, annually for critical apps
258
259
**Quick Steps:**
260
1. **Stabilize:** Wait 15-30 min (space), 30 min (duct with system running)
261
2. **Position reference:** Within 6" of sensor, same height/location
262
3. **Wait:** 2-3 min for reference to stabilize
263
4. **Compare:**
264
- Sensor reading: ______°F
265
- Reference reading: ______°F
266
- Error: ______ °F
267
5. **Acceptable:** ±2°F for most BAS, ±1°F for tight tolerance apps
268
269
**If Outside Tolerance:**
270
- **Option A (Preferred):** Apply controller calibration offset
271
- Access controller config for this input
272
- Enter offset value (+ if sensor reads low, - if reads high)
273
- Verify reading now matches reference
274
- Document offset in Service Fusion
275
276
- **Option B:** Adjust sensor (if has calibration pot)
277
- Remove cover, locate adjustment screw
278
- Adjust while monitoring reading
279
- Re-verify with reference
280
281
- **If Cannot Calibrate:** Replace sensor
282
283
**Document:** Tech name, date, reference ID & cal date, before/after readings
284
285
---
286
287
## COMMON ISSUES & TIPS
288
289
**Space sensors reading high:** Check if in direct sun or near heat source
290
**Duct sensors inaccurate:** Verify insertion depth (1/3 width for spot sensing)
291
**Outdoor sensors erratic:** Ensure north-facing, away from exhaust/relief dampers
292
**Immersion sensors slow:** Normal - thermal mass requires 15-20 min to respond
293
**All sensors offset same amount:** Apply controller calibration offset, don't replace
294
**Shielded cable:** Ground shield at controller end ONLY (not both ends)
295
**10K Type II vs Type III:** Most controllers auto-detect, but verify in config
296
297
---
298
299
**Document ID:** SSO-TEMP-001
300
**Revision:** 1.0
301
**Next Review:** Dec 2026