Glycol Hot Water System (HWS) - Sequence of Operation
Version: 1.0 Date: 2025-12-29 Author: Gemini Agent Related SSO: SSO Temp Sensor, SSO Pressure Sensor, SSO Valve Actuator, SSO Relay Output
1. Overview
This document outlines the sequence of operation for the Glycol Hot Water System (HWS), which provides heating capacity to the facility. The system initiates operation either automatically based on outside air temperature (OAT) conditions or via manual activation from the User workstation.
Key functions of this system include:
- System Activation & Temperature Control: Hot water pumps are started, and upon proving operation, heat exchanger valves modulate to maintain a hot water supply temperature setpoint. This setpoint dynamically resets as a function of OAT to optimize energy usage.
- Differential Pressure Control: A differential pressure transmitter located in the main hot water supply piping modulates a bypass valve to ensure a constant differential pressure is maintained across the supply and return mains.
- Glycol Make-up Automation: An integrated glycol make-up pump system automatically monitors and maintains the system pressure, activating the pump when necessary and ensuring safe operation with various pressure and level alarms.
The system is controlled by an ECL-650 controller, which monitors and manages all associated points and alarms.
2. Point List
Inputs (Physical)
- Hot Water Pump 7 Status (P-7-S): BI (ECL-650, UI1), Dry Contact
- Hot Water Pump 8 Status (P-8-S): BI (ECL-650, UI2), Dry Contact
- Glycol Tank Low Level Alarm (GT-LL-A): BI (ECL-650, UI3), Dry Contact
- Hot Water Pump 9 Status (P-9-S): BI (ECL-650, UI4), Dry Contact
- Glycol Hot Water Differential Pressure Transducer (HWS-DP): AI (ECL-650, UI5), 0-10VDC
- Hot Water Supply Temperature (HWS-T): AI (ECL-650, UI6), 1K RTD
- Hot Water Return Temperature (HWR-T): AI (ECL-650, UI7), 1K RTD
Outputs (Physical)
- Hot Water Pump 7 Command (P-7-C): BO (ECL-650, UO1), 12 VDC
- Hot Water Pump 8 Command (P-8-C): BO (ECL-650, UO2), 12 VDC
- Hot Water Pump 9 Command (P-9-C): BO (ECL-650, UO3), 12 VDC
- Glycol Hot Water Bypass Valve Output (HW-BYP-VLV-O): AO (ECL-650, UO4), 0-10VDC
- Heat Exchanger Control Valve 1 Output (HX-1-O): AO (ECL-650, UO5), 0-10VDC
- Heat Exchanger Control Valve 2 Output (HX-2-O): AO (ECL-650, UO6), 0-10VDC
Software Points & Setpoints
- Heat Exchanger Differential Pressure Setpoint (HX-1-DP-SP): Setpoint (Software)
- Hot Water Supply Temperature Setpoint (HWS-SP): Setpoint (Software)
- Hot Water System ON/OFF Command (HWS-RUN): Software (from User Workstation or OAT)
- Outside Air Temperature (OAT): AI (Networked or Local)
- Hot Water Supply Temp High Limit Alarm (HWS-T-HILMT): Setpoint (Software)
- Hot Water Supply Temp Low Limit Alarm (HWS-T-LOLMT): Setpoint (Software)
- Glycol System Normal Operating Pressure (GCHW-Press-SP): Setpoint (Software)
- Glycol System Low-Low Pressure Alarm Limit (GCHW-Press-LOLMT): Setpoint (Software)
- Glycol System High-High Pressure Alarm Limit (GCHW-Press-HILMT): Setpoint (Software)
3. Safety Devices & Interlocks
- System Activation Interlock: Heat exchanger valves (
HX-1-O,HX-2-O) will only be activated upon confirmation of operation (P-7-S,P-8-S,P-9-S) of the associated hot water pumps. - Glycol Pump Pressure Safety: The glycol make-up pump (P-9) will be de-energized if the system pressure drops below a low-low limit setpoint (
GCHW-Press-LOLMT) or rises above a high-high limit setpoint (GCHW-Press-HILMT). An alarm is generated in both cases. - Glycol Pump Start Failure: If the make-up pump (P-9) is commanded ON (
P-9-C) but its corresponding status contact (P-9-S) does not prove operation within a defined time, the pump command will be stopped and a malfunction alarm will be generated. - Glycol Tank Low Level: If the glycol tank low level float switch (
GT-LL-A) activates, the associated make-up pump (P-9) will be stopped, and an alarm will be generated to prevent the pump from running dry.
4. Modes of Operation
Hot Water System Start/Stop
- System Start Conditions:
- Automatic: Outside Air Temperature (
OAT) drops below 60°F (adjustable). - Manual: Activated via the User workstation (
HWS-RUN).
- Automatic: Outside Air Temperature (
- System Stop Conditions:
- Automatic: Outside Air Temperature (
OAT) rises above 60°F (adjustable) ANDHWS-RUNis OFF. - Manual: Deactivated via the User workstation (
HWS-RUN).
- Automatic: Outside Air Temperature (
- Start Sequence:
- Upon start condition, hot water pumps (
P-7-C,P-8-C,P-9-C) are commanded ON. - Upon confirmation of pump operation (via
P-7-S,P-8-S,P-9-Sauxiliary contacts), heat exchanger valves (HX-1-O,HX-2-O) are activated.
- Upon start condition, hot water pumps (
Hot Water Supply Temperature Control
- Objective: Maintain
HWS-TatHWS-SP. - Control Action: The one-third two-third steam control valves (implied by
HX-1-O,HX-2-O) will be modulated, in sequence, to maintain the desiredHWS-SP. - Setpoint Reset Schedule: The
HWS-SPwill be reset as a function ofOATin accordance with the following schedule (user adjustable):- OAT < 20°F:
HWS-SP= 180°F - OAT = 40°F:
HWS-SP= 160°F - OAT > 60°F:
HWS-SP= 140°F (Minimum setpoint, system likely OFF) - Linear interpolation between these points.
- OAT < 20°F:
Hot Water Differential Pressure Control
- Objective: Maintain a constant differential pressure (
HWS-DP) across the hot water supply and hot water return mains. - Control Action: The
HWS-DPtransmitter modulates the normally open hot water differential pressure bypass valve (HW-BYP-VLV-O).- If
HWS-DPdrops below its setpoint, the bypass valve modulates closed. - If
HWS-DPrises above its setpoint, the bypass valve modulates open.
- If
Glycol Make-up Pump (P-9) Control
- Monitoring: An analog pressure transmitter (assumed part of
HWS-DPor a separate sensor) in the expansion tank feed line continuously monitors system pressure. - Pump Activation: If system pressure drops below the
GCHW-Press-SP, the glycol make-up pump (P-9, commanded viaP-9-C) is activated. - Pump Deactivation: The pump runs continuously until system pressure rises to meet or exceed the
GCHW-Press-SP. - Safety Stop: The pump is stopped if system pressure drops below
GCHW-Press-LOLMTor rises aboveGCHW-Press-HILMT.
5. Alarms & Fault Conditions
All alarms shall be annunciated at the User workstation.
- Hot Water Pump Failure:
- Condition: Status contact (
P-7-S,P-8-S,P-9-S) indicates a pump is off when it should be running. - Priority: High.
- Condition: Status contact (
- Hot Water Supply Temperature Out of Range:
- Condition: The
HWS-Treading exceeds the high (HWS-T-HILMT) or low (HWS-T-LOLMT) alarm limits. - Priority: Medium.
- Condition: The
- Glycol Pump Pressure Alarm:
- Condition: System pressure drops below
GCHW-Press-LOLMTor rises aboveGCHW-Press-HILMT. - Priority: High.
- Condition: System pressure drops below
- Glycol Pump Malfunction:
- Condition: The glycol make-up pump (P-9) fails to prove status after being commanded ON.
- Priority: High.
- Glycol Tank Low Level:
- Condition: The low level float switch (
GT-LL-A) is activated. - Priority: Critical. Prevents pump operation.
- Condition: The low level float switch (
6. Commissioning & Verification Checklist
- Verify the hot water system starts automatically when
OATdrops below 60°F and stops whenOATrises above 60°F (and manual command is OFF). - Verify the hot water system can be manually started and stopped from the User workstation.
- Verify all hot water pumps (
P-7-C,P-8-C,P-9-C) activate upon system start. - Verify heat exchanger valves (
HX-1-O,HX-2-O) activate only after pump operation is confirmed (P-7-S,P-8-S,P-9-S). - Verify
HWS-Tsetpoint resets according to theOATschedule (e.g., 180°F at 20°F OAT, 160°F at 40°F OAT, 140°F at 60°F OAT). - Verify heat exchanger valves modulate to maintain the
HWS-SP. - Verify the
HWS-DPreading is accurate. With pumps running, adjust load conditions and observeHW-BYP-VLV-Omodulating to maintain theHWS-DPsetpoint. - Simulate a hot water pump failure (e.g., disconnect
P-7-S) and verify a “Hot Water Pump Failure” alarm is generated. - Adjust the high and low alarm limits for
HWS-Tand verify that an alarm is generated when the temperature goes out of range. - Simulate a drop in system pressure and verify the glycol make-up pump (P-9) activates.
- Verify the make-up pump deactivates once the
GCHW-Press-SPis achieved. - Simulate a system pressure drop below
GCHW-Press-LOLMTand verify the make-up pump is stopped and an alarm is generated. - Simulate a system pressure rise above
GCHW-Press-HILMTand verify the make-up pump is stopped and an alarm is generated. - With the make-up pump commanded on, disconnect its status input (
P-9-S) and verify a “Glycol Pump Malfunction” alarm is generated. - Manually activate the
GT-LL-Afloat switch and verify the make-up pump (P-9) is de-energized and a “Glycol Tank Low Level” alarm is generated.
Document Owner: Technical Training Department
Last Updated: December 2025
Next Review: March 2026
Feedback: training@example.com
“A well-controlled hot water system is the backbone of comfort and energy efficiency.”