Temperature Sensor - Quick Reference SSO
Device Type: Analog Input - Sensor
Signal: Thermistor (10K) / 0-10VDC / 4-20mA
Power: Unpowered (thermistor) / 24VAC-VDC (transmitter)
Version: 1.0 | Date: Dec 2025
DEVICE OVERVIEW
Common Models:
- Johnson Controls TE-6000, Honeywell T7350, Siemens QAA, Belimo 22RT, BAPI BA/10K
Used For:
Space temperature, duct air temp, immersion (water/glycol), outdoor air sensing
Wire Type: 18AWG minimum, 16AWG recommended, shielded if >50ft
Environment: Space 32-120°F | Duct -40-200°F | Immersion -40-250°F
SAFETY - PPE REQUIRED
- ☑ Safety glasses (ANSI Z87.1)
- ☑ Cut-resistant gloves (sheet metal)
- ☑ Hard hat (mechanical rooms/rooftops)
- ☑ Dust mask (drilling ducts)
- ☑ Fall protection (if >6 feet height)
HAZARDS
- ⚠ Sharp edges - Sheet metal ductwork
- ⚠ Hot/cold surfaces - Ducts near coils, pipes
- ⚠ Falls - Ladder work, rooftop access
- ⚠ Rotating equipment - Air handler fans (LOTO required)
LOCKOUT/TAGOUT
- Required for duct sensors: Lock out air handler before drilling duct
- Notify building operator
- Lock breaker with personal lock
- Test that fan won’t start
- Remove lock only after work complete
INSTALLATION CHECKLIST
TOOLS NEEDED
- Drill + bits (1/16”-1/2”)
- Hole saw (3/4”-1” for duct)
- Wire strippers (18-16 AWG)
- Multimeter (DMM)
- Level, tape measure
- Deburring tool
- Duct sealant (high-temp)
- Label maker
PRE-INSTALL
- Location per blueprints verified
- Space sensor: Away from sun, exterior walls, diffusers (6ft), doors (3ft)
- Duct sensor: Straight section (3× duct diameter from elbows)
- Outside sensor: North wall, away from exhaust (10ft)
- Correct sensor type for controller input (thermistor vs transmitter)
INSTALL STEPS - SPACE SENSOR
- Mount: 48-60” above floor, interior wall, use level
- Route Wire: Through wall/conduit, 12” service loop
- Terminate (Thermistor 2-wire):
- Wire 1 (Red): Terminal 1
- Wire 2 (Black): Terminal 2
- Polarity doesn’t matter for thermistor
- Terminate (Transmitter 3-wire):
- Red: +24VAC/VDC
- Black: Common/Ground
- White/Green: Signal output
- Label: “RM-[#]-TEMP” both ends
- Install cover and verify level
INSTALL STEPS - DUCT SENSOR
- LOCKOUT air handler before starting
- Mark location: Straight duct, avoid seams/ribs
- Drill penetration: Pilot hole → Hole saw → Deburr edges
- Insert probe: 1/3 duct width (spot) or full width (averaging)
- Secure flange: Sheet metal screws, tight but not distorted
- Seal penetration: High-temp duct sealant, no air leaks
- Terminate wiring: Per sensor type (above)
- Restore system: Remove lockout, verify fan starts
INSTALL STEPS - IMMERSION SENSOR
- Verify thermowell present in pipe
- Apply thermal compound to probe tip
- Insert probe fully into thermowell
- Tighten compression fitting: Hand tight + 1/4 turn with wrench
- Terminate wiring and support with cable ties
POST-INSTALL
- Device mounted securely and level
- All wires tight (7-9 in-lbs torque)
- Labels applied both ends
- Duct penetrations sealed (no leaks)
- Work area cleaned
- Photos taken
EXPECTED READINGS
PRE-POWER (Power OFF)
THERMISTOR (2-wire, unpowered):
- Resistance at 70°F: 9,500 - 10,500 ohms (10K Type II/III)
- At 60°F: ~12,500 ohms
- At 80°F: ~8,000 ohms
- If infinity: Open circuit - failed sensor or broken wire
- If near zero: Short circuit
TRANSMITTER (3-wire):
- Continuity: Each wire <5 ohms end-to-end
ISOLATION: >10K ohms to ground (all types)
POWER-UP
THERMISTOR:
- Controller provides excitation (~5VDC)
- Controller converts resistance to temperature
TRANSMITTER:
- Supply Voltage: 24VAC/VDC ±10% (21.6-26.4V acceptable)
- Output at 70°F (0-10V, 0-100°F range): ~7.0V
- Output at 70°F (4-20mA, 0-100°F range): ~15.2mA
ACCEPTABLE RANGE - SPACE TEMP
- ✓ Reading: 68-72°F at room temp (±2°F initially acceptable)
- ✓ Response time: 30-90 seconds to stabilize
- ✓ Controller shows reading (no faults)
- ✓ Graphics display live value
TYPICAL READINGS - DUCT
- Supply Air Cooling: 50-60°F
- Supply Air Heating: 90-120°F
- Return Air: 68-76°F
- Outside Air: Matches local weather (±5°F)
TYPICAL READINGS - IMMERSION
- Chilled Water Supply: 42-48°F
- Chilled Water Return: 52-58°F
- Hot Water Supply: 140-180°F
- Condenser Water: 70-95°F
PROOF OUT TESTS
TEST 1: Response Test
- Do: Place hand over space sensor (or heat duct sensor with breath)
- Expect: Reading increases 3-8°F within 30-60 seconds
- Pass If: Reading changes and returns to baseline when removed
TEST 2: Accuracy Check
- Do: Compare to calibrated reference thermometer (within 6”)
- Expect: Reading within ±2°F of reference
- Pass If: Within tolerance after 5 min stabilization
TEST 3: Stability Check
- Do: Monitor reading for 5 minutes
- Expect: Stable reading (±1°F variation max)
- Pass If: No erratic jumping or oscillation
TEST 4: Controller Integration
- Device appears in controller point list
- Reading displays correctly (no faults)
- Graphics show live data updating
- Control system responds to sensor (heating/cooling calls)
TROUBLESHOOTING
NO POWER / NO READING / FAULT
- Thermistor: Measure resistance at sensor: Should be ~10K at 70°F
- If infinity: Replace sensor (open circuit)
- If near zero: Replace sensor (short circuit)
- Transmitter: Check supply voltage at sensor: 24V ±10%
- Test continuity end-to-end: <5 ohms
- Check all terminal connections tight
- Verify polarity correct (transmitters only)
- If still dead: Replace device
READING TOO HIGH OR LOW (Offset)
- Compare to calibrated reference thermometer
- Space sensor: Check for influences:
- Direct sunlight, heat sources, cold surfaces
- Too close to diffuser (<6ft) or exterior wall
- Duct sensor: Verify insertion depth (1/3 width typical)
- Immersion sensor: Verify probe fully inserted in thermowell
- Wait 30 min for stabilization
- If consistently off by same amount: Apply controller calibration offset
- If off by >5°F: Relocate or replace sensor
ERRATIC / JUMPING READINGS
- Check all terminal connections tight (wiggle test)
- Inspect wiring for damage, pinching
- Check for EMI/RFI interference:
- Wire running parallel to power cables?
- Near motors, VFDs, transformers?
- Verify shielded cable used if required (>50ft runs)
- Test at sensor AND at controller (same reading?)
- Look for moisture in connections
- If wiring OK: Replace sensor
SLOW RESPONSE
- Normal: 30-90 seconds for most sensors
- Duct sensor: May be outside airstream - check depth
- Check for buildup on sensor element
- If >2 minutes consistently: Clean or replace
ESCALATION - COMPLETE BEFORE CALLING
PRE-ESCALATION CHECKLIST
- Verified supply voltage at sensor (transmitters: 24V ±10%)
- Tested sensor resistance (thermistors: ~10K at 70°F)
- Verified all wire connections tight and correct
- Tested continuity end-to-end (<5 ohms)
- Compared to calibrated reference thermometer
- Checked for environmental influences
- Verified sensor type matches controller input config
- Documented all readings with multimeter
- Taken photos of installation and wiring
- Reviewed sensor installation manual
PROVIDE THIS INFO
- Device: [Mfg / Model / Location]
- Sensor Type: Thermistor / 0-10V / 4-20mA
- Measured Resistance: _____ ohms (thermistors)
- Supply Voltage: _____ V (transmitters)
- Output Signal: _____ V or mA
- Controller Reading: _____ °F
- Reference Reading: _____ °F
- Error: _____ °F (sensor - reference)
- Environment: Temp ____ / Humidity ____ / Airflow ____
- Steps Taken: [List troubleshooting completed]
- Photos: Attached to Service Fusion ticket
CONTACTS
- Field Specialist: [Phone]
- Programmer: [Phone] (if calibration offset needed)
- Project Manager: [Phone] (if design/location issue)
- Dispatch: [Phone] (parts/resources)
CALIBRATION
When Required: All sensors verified during commissioning, annually for critical apps
Quick Steps:
- Stabilize: Wait 15-30 min (space), 30 min (duct with system running)
- Position reference: Within 6” of sensor, same height/location
- Wait: 2-3 min for reference to stabilize
- Compare:
- Sensor reading: ______°F
- Reference reading: ______°F
- Error: ______ °F
- Acceptable: ±2°F for most BAS, ±1°F for tight tolerance apps
If Outside Tolerance:
-
Option A (Preferred): Apply controller calibration offset
- Access controller config for this input
- Enter offset value (+ if sensor reads low, - if reads high)
- Verify reading now matches reference
- Document offset in Service Fusion
-
Option B: Adjust sensor (if has calibration pot)
- Remove cover, locate adjustment screw
- Adjust while monitoring reading
- Re-verify with reference
-
If Cannot Calibrate: Replace sensor
Document: Tech name, date, reference ID & cal date, before/after readings
COMMON ISSUES & TIPS
✓ Space sensors reading high: Check if in direct sun or near heat source
✓ Duct sensors inaccurate: Verify insertion depth (1/3 width for spot sensing)
✓ Outdoor sensors erratic: Ensure north-facing, away from exhaust/relief dampers
✓ Immersion sensors slow: Normal - thermal mass requires 15-20 min to respond
✓ All sensors offset same amount: Apply controller calibration offset, don’t replace
✓ Shielded cable: Ground shield at controller end ONLY (not both ends)
✓ 10K Type II vs Type III: Most controllers auto-detect, but verify in config
Document ID: SSO-TEMP-001
Revision: 1.0
Next Review: Dec 2026