Pressure Sensor (Differential) - Quick Reference SSO
Device Type: Analog Input - Pressure Sensor
Signal: 0-10VDC / 4-20mA output
Power: 24VAC/VDC (powered transmitter)
Version: 1.0 | Date: Dec 2025
DEVICE OVERVIEW
Common Models:
- Setra 264/265/267, Honeywell ST3000, Dwyer 629/679, Johnson Controls P499, Belimo 22DT
Used For:
Duct static pressure (supply/return), filter status, room pressurization, airflow measurement, building pressure
Specifications:
- Range: Common ranges:
- 0-0.5” W.C. (filter status, low static)
- 0-1” W.C. (duct static, most common)
- 0-2” W.C. (high static, fans)
- 0-5” W.C. (high pressure applications)
- Accuracy: ±1% of full scale typical
- Output: 0-10VDC or 4-20mA proportional to pressure
- Power: 24VAC or 24VDC, 20-50mA consumption
- Wire Type: 18AWG minimum
- Wiring: 3-wire (power, common, signal) + 2 pressure tubes
Environment: 32-122°F, 0-95% RH non-condensing
SAFETY - PPE REQUIRED
- ☑ Safety glasses (ANSI Z87.1)
- ☑ Work gloves
- ☑ Hard hat (mechanical rooms)
- ☑ Dust mask (drilling ducts)
HAZARDS
- ⚠ ROTATING EQUIPMENT - Fans, blowers (LOCKOUT required if accessing)
- ⚠ SHARP EDGES - Sheet metal ductwork
- ⚠ PRESSURIZED SYSTEMS - Ductwork under positive pressure
- ⚠ HOT/COLD SURFACES - Supply ducts near coils
LOCKOUT/TAGOUT
- Required if accessing fan section: Lock out air handler before installing duct probes
- NOT required for remote wall-mounted sensors with existing pressure taps
INSTALLATION CHECKLIST
TOOLS NEEDED
- Drill + bits (1/4” for duct penetrations)
- Wire strippers (18AWG)
- Multimeter (DMM)
- Level
- Tubing cutter
- Pressure probe kit
- Duct sealant
- Label maker
MATERIALS
- Pressure tubing (vinyl, 1/4” OD typical)
- Duct pressure probes (if not pre-installed)
- Tube fittings for sensor
- Cable ties
- Duct sealant
PRE-INSTALL
- Verify sensor range matches application (0-1” W.C. most common for duct static)
- Confirm sensor type matches controller input (0-10V vs 4-20mA)
- Identify high and low pressure tap locations per blueprints
- For duct sensors: Locate in straight section (3× duct diameter from elbows)
INSTALL STEPS
WALL-MOUNTED SENSOR (Typical Installation):
-
Mount sensor:
- Location accessible for service
- Protected from weather if outdoor
- Use level to ensure horizontal
- Near pressure tap locations (minimize tube length)
-
Install duct pressure probes (if not existing):
- LOCKOUT air handler first
- Drill 1/4” holes in duct at marked locations
- Insert pressure probe through hole
- Probe orientation: Open end facing upstream (into airflow)
- Seal around probe with duct sealant
- For static pressure: One probe in supply duct, one in return (or reference to room)
- For filter ΔP: One probe upstream of filter, one downstream
-
Route pressure tubing:
- Connect tubing to duct probes
- Route tubing to sensor location
- Support tubing every 3-4 feet with cable ties
- Avoid kinks or sharp bends
- Slope tubing toward sensor (prevents condensation accumulation)
- Keep tube length <50 feet if possible (shorter = faster response)
-
Connect tubing to sensor:
- High pressure port: Connect to upstream probe or higher pressure location
- Low pressure port: Connect to downstream probe or lower pressure location
- Push tubing firmly into fittings (click or resistance indicates seated)
- IMPORTANT: Reversed ports will give negative reading
-
Route and terminate electrical wiring:
- 3-Wire Standard:
- Red: +24VAC/VDC power
- Black: Common
- White/Green: Signal output (0-10V or 4-20mA)
- Tighten terminals: 7-9 in-lbs
- Leave 12” service loop
- 3-Wire Standard:
-
Label wiring and tubing:
- Wire label: “AHU-1-STATIC” or “FILTER-DP”
- Tube labels: “HIGH” and “LOW” at sensor connections
- Label both ends of wiring
-
Restore system (if locked out)
POST-INSTALL
- Sensor mounted securely and level
- Both pressure probes installed and sealed
- Tubing connected to correct ports (HIGH/LOW)
- No kinks or restrictions in tubing
- Tubing sloped toward sensor
- All wiring terminated tight
- Labels applied
- Work area cleaned
- Photos taken
EXPECTED READINGS
PRE-POWER (Power OFF)
- Continuity: Each wire <5 ohms end-to-end
- Isolation: >10K ohms to ground
- Pressure Tubing: Blow through tubes to verify not blocked
POWER-UP
- Supply Voltage: 24VAC/VDC ±10% (21.6-26.4V)
- Power Consumption: 20-50mA typical
- Zero Pressure Reading: With no pressure difference, sensor should read 0” W.C. (or very close)
NORMAL READINGS - DUCT STATIC PRESSURE
| Application | Typical Range | 0-10V Output (0-1” range) |
|---|---|---|
| Supply duct (fan off) | 0” W.C. | 0V |
| Supply duct (fan low speed) | 0.2-0.4” W.C. | 2-4V |
| Supply duct (fan normal) | 0.5-0.8” W.C. | 5-8V |
| Supply duct (fan high speed) | 0.8-1.2” W.C. | 8-10V+ |
ASHRAE Recommendations:
- Supply duct static: 0.5-1.0” W.C. typical
- Return duct static: 0.1-0.3” W.C. typical
NORMAL READINGS - FILTER DIFFERENTIAL PRESSURE
| Filter Condition | Typical ΔP | 0-10V Output (0-1” range) |
|---|---|---|
| New/clean filter | 0.05-0.15” W.C. | 0.5-1.5V |
| Normal filter | 0.2-0.4” W.C. | 2-4V |
| Dirty filter (replace) | 0.5-0.8” W.C. | 5-8V |
| Severely plugged | >1.0” W.C. | >10V |
Filter Change Threshold: Typically 0.5-1.0” W.C. depending on filter type
NORMAL READINGS - BUILDING PRESSURIZATION
| Application | Typical Range |
|---|---|
| Operating rooms (positive pressure) | +0.01 to +0.05” W.C. |
| Isolation rooms (negative pressure) | -0.01 to -0.05” W.C. |
| Labs (negative pressure) | -0.02 to -0.10” W.C. |
| Data centers (slight positive) | +0.01 to +0.03” W.C. |
PROOF OUT TESTS
TEST 1: Zero Check
- Do: Disconnect both pressure tubes from sensor (open to atmosphere)
- Expect: Reading should be 0” W.C. (±0.01”)
- Pass If: Reads within ±0.01” W.C. of zero
- If not zero: Some sensors have zero adjustment - calibrate per manual
TEST 2: Tube Orientation Test
- Do: With system running, note current reading
- Do: Swap HIGH and LOW tubes at sensor
- Expect: Reading should reverse sign (positive becomes negative)
- Pass If: Sign reverses - confirms tubes connected correctly
- Do: Swap tubes back to correct orientation
TEST 3: Response Test
- Do: Start/stop fan (or change fan speed)
- Expect: Reading changes proportionally within 5-10 seconds
- Pass If: Reading responds to pressure changes
TEST 4: Tube Blockage Test
- Do: Gently blow into LOW pressure tube (disconnect from sensor first)
- Expect: Can blow through easily, feel air at duct probe
- Pass If: No blockage detected
- Repeat for HIGH pressure tube
TEST 5: Controller Integration
- Sensor appears in controller AI list
- Reading displays in inches W.C.
- Graphics show live data
- Controller uses reading for fan/damper control
- No faults or errors
TROUBLESHOOTING
NO READING / ZERO ALL THE TIME
- Verify supply voltage at sensor: 24VAC/VDC ±10%
- Check output signal: Should be 0-10V or 4-20mA (not fixed at 0V/4mA)
- Verify pressure tubing connected to both ports
- Blow through tubes to check for blockages
- Check duct probes not plugged with dirt/debris
- If sensor has power but reads zero with system running: Tubes may be reversed or blocked
READING NEGATIVE (When Should Be Positive)
- HIGH and LOW tubes reversed - swap tubes at sensor
- Verify duct probe orientation (open end into airflow)
- Check that controller input not configured backwards
READING TOO HIGH OR TOO LOW
- Verify sensor range matches application:
- Filter ΔP typically needs 0-1” W.C. or 0-2” W.C. range
- Duct static typically 0-1” W.C. range
- High static fans may need 0-2” or 0-5” W.C. range
- Check for kinked or restricted tubing
- Verify duct probe locations per design (not in turbulent area)
- Compare to handheld pressure meter (Magnehelic or digital)
- If consistently offset: Calibrate zero point
ERRATIC / FLUCTUATING READING
- Check for water condensation in pressure tubing:
- Disconnect tubes and blow out water
- Improve tubing slope toward sensor
- Consider installing drip legs or water traps
- Verify duct probes in smooth, straight duct section (not near elbows, dampers)
- Check for air leaks in tubing connections
- Look for tubing vibration (fan vibration transmitted through tubes)
- If persists: Replace sensor (diaphragm may be damaged)
SLOW RESPONSE
- Check pressure tubing length (>50 feet = slower response)
- Verify tubing not kinked or restricted
- Check tubing diameter adequate (1/4” OD typical)
- Look for water accumulation in tubes
- Note: Some slow response is normal for long tube runs (10-30 seconds)
READING DRIFTS OVER TIME
- Temperature compensation issue - verify sensor in stable temp environment
- Check zero point calibration
- If drifts significantly: Replace sensor (diaphragm aging)
ESCALATION - COMPLETE BEFORE CALLING
PRE-ESCALATION CHECKLIST
- Verified supply voltage at sensor (24V ±10%)
- Verified pressure tubes connected to correct ports (HIGH/LOW)
- Blown through tubes to check for blockages
- Checked duct probes not plugged with debris
- Verified sensor range appropriate for application
- Compared to handheld pressure meter (if available)
- Checked for water in pressure tubing
- Documented readings with system on/off
- Taken photos of installation
PROVIDE THIS INFO
- Sensor: [Mfg / Model / Range / Location]
- Application: Duct static / Filter ΔP / Room pressure / Other
- Supply Voltage: _____ VAC/VDC
- Output Signal: 0-10V or 4-20mA
- Current Reading: _____ ” W.C.
- Expected Reading: _____ ” W.C. (based on application)
- Handheld Meter Reading: _____ ” W.C. (if available)
- System Status: Fan on/off, speed ____%
- Tube Length: _____ feet (HIGH and LOW)
- Symptoms: [Zero, negative, high, low, erratic, slow]
- Steps Taken: [Troubleshooting completed]
CONTACTS
- Field Specialist: [Phone]
- Programmer: [Phone] (if control sequence issue)
- Project Manager: [Phone]
- Dispatch: [Phone]
CALIBRATION
When Needed:
- After installation (zero check)
- Annually or if reading drifts
- After sensor replacement
Zero Calibration:
- Disconnect both pressure tubes from sensor (open to atmosphere)
- Wait 2 minutes for stabilization
- Reading should be 0” W.C. (±0.01”)
- If not zero:
- Some sensors have zero adjustment screw/button
- Or apply controller offset
- Reconnect tubes and retest
Span Calibration (if available on sensor):
- Requires calibrated pressure source (hand pump with gauge)
- Apply known pressure (e.g., 0.5” W.C. for 0-1” range)
- Adjust sensor span to match applied pressure
- Note: Most sensors are factory calibrated and don’t require span adjustment
Acceptable Tolerance: ±1% of full scale (0.01” W.C. for 0-1” range)
COMMON ISSUES & TIPS
✓ Tube orientation: HIGH port to upstream probe, LOW port to downstream/reference
✓ Tube length: Keep <50 feet for faster response, slope toward sensor
✓ Water in tubes: Common problem - install drip legs or blow out regularly
✓ Probe location: Straight duct section, avoid turbulent areas near elbows/dampers
✓ Probe orientation: Open end facing into airflow (upstream)
✓ Filter ΔP alarms: Typically set at 0.5-1.0” W.C. for filter change notification
✓ Static pressure control: Used for VFD fan speed control, maintains constant pressure
✓ Building pressure: Critical for healthcare, labs, clean rooms - requires tight tolerance sensors
✓ Negative readings: Usually indicate reversed tubes or wrong probe orientation
✓ Range selection: Match sensor range to application - oversized range reduces accuracy
✓ Magnehelic gauge: Mechanical pressure gauge useful for field verification (no power required)
Document ID: SSO-PRESSURE-001
Revision: 1.0
Next Review: Dec 2026