Blame

e0f744 root 2026-05-15 18:36:28
Add all documentation pages and update home index
1
# Glycol Chilled Water System (CHWS) - Sequence of Operation
2
3
**Version:** 1.0
4
**Date:** 2025-12-29
5
**Author:** Gemini Agent
740841 root 2026-05-15 19:21:41
Refactor repository to kebab-case and update all internal links
6
**Related SSO:** [[training-structure/sso/sso-temp-sensor]], [[training-structure/sso/sso-pressure-sensor]], [[training-structure/sso/sso-flow-switch]], [[training-structure/sso/sso-valve-actuator]], [[training-structure/sso/sso-relay-output]]
e0f744 root 2026-05-15 18:36:28
Add all documentation pages and update home index
7
8
---
9
10
## 1. Overview
11
This document outlines the sequence of operation for the Glycol Chilled Water System (CHWS). This is a manually-started system during the cooling season, featuring monitoring and control of multiple chilled water pumps, chillers, and associated glycol make-up units.
12
13
The system's primary automated functions are:
14
1. **System Monitoring & Alarming**: Upon manual activation, the control panel actively monitors pump status, water flow, temperatures, and pressures. It generates alarms for any out-of-spec conditions, including pump failure, loss of flow, or abnormal temperatures.
15
2. **Differential Pressure Control**: A differential pressure transmitter located in the main piping loop continuously modulates a bypass valve to maintain a constant differential pressure between the supply and return mains.
16
3. **Glycol Make-up Automation**: Dedicated glycol make-up pump systems automatically maintain pressure in their associated loops. The pump activates to build pressure and deactivates upon reaching the setpoint, with full safety and level monitoring alarms.
17
18
The system is managed by two `ECL-650` controllers, which handle specific pumps, fans, and chillers but share common system sensors.
19
20
---
21
22
## 2. Point List
23
*Note: The system is controlled by two separate ECL-650 controllers. The controller for each point is noted below.*
24
25
### Inputs (Physical)
26
- **Chilled Water Pump 1 Status (P-1-S)**: BI (ECL-650 (1), UI1), Dry Contact
27
- **Chilled Water Pump 2 Status (P-2-S)**: BI (ECL-650 (1), UI2), Dry Contact
28
- **Chilled Water Pump 3 Status (P-3-S)**: BI (ECL-650 (1), UI5), Dry Contact
29
- **Chilled Water Pump 4 Status (P-4-S)**: BI (ECL-650 (2), UI1), Dry Contact
30
- **Chilled Water Pump 5 Status (P-5-S)**: BI (ECL-650 (2), UI2), Dry Contact
31
- **Chilled Water Pump 6 Status (P-6-S)**: BI (ECL-650 (2), UI5), Dry Contact
32
- **Chilled Water System Flow Switch (Existing) (FLOW-S)**: BI (Both ECL-650, UI3), Dry Contact
33
- **Glycol Tank Low Level Alarm (GT-LL-A)**: BI (Both ECL-650, UI4), Dry Contact
34
- **Exhaust Fan 4 Status (EF-4-S)**: BI (ECL-650 (1), UI6), Dry Contact
35
- **Exhaust Fan 19 Status (EF-19-S)**: BI (ECL-650 (1), UI7), Dry Contact
36
- **Exhaust Fan 7 Status (EF-7-S)**: BI (ECL-650 (2), UI6), Dry Contact
37
- **Exhaust Fan 20 Status (EF-20-S)**: BI (ECL-650 (2), UI7), Dry Contact
38
- **Glycol Chilled Water Differential Pressure Transducer (GCHW-DP)**: AI (Both ECL-650, UI8), 0-10VDC
39
- **Chilled Water Supply Temperature (GCHWS-T)**: AI (Both ECL-650, UI9), 10K Type II
40
- **Chilled Water Return Temperature (GCHWR-T)**: AI (Both ECL-650, UI10), 10K Type II
41
- **Outside Air Humidity (OA-H)**: AI (ECL-650 (1), UI11), 0-10 VDC
42
- **Outside Air Temperature (OA-T)**: AI (ECL-650 (1), UI12), 10K Type II
43
- **Chiller 1 Common Alarm (CH-COM-A)**: BI (ECL-650 (1), UI13), Dry Contact
44
- **Chiller 2 Common Alarm (CH-COM-A)**: BI (ECL-650 (2), UI12), Dry Contact
45
- **Chiller 1 Differential Pressure (CH-1-DP)**: AI (ECL-650 (1), UI14), 0-10VDC
46
- **Chiller 2 Differential Pressure (CH-2-DP)**: AI (ECL-650 (2), UI13), 0-10VDC
47
- **Heat Exchanger 1 Differential Pressure (HX-1-DP)**: AI (ECL-650 (2), UI11), 0-10VDC
48
- **Outside Air Temperature (OA-T)**: AI (Via Network), Global
49
- **Outside Air Humidity (OA-H)**: AI (Via Network), Global
50
51
### Outputs (Physical)
52
- **Exhaust Fan 4 Command (EF-4-C)**: BO (ECL-650 (1), UO1), 12VDC
53
- **Exhaust Fan 19 Command (EF-19-C)**: BO (ECL-650 (1), UO2), 12VDC
54
- **Pump 3 (Glycol Make-up) Command (P-3-C)**: BO (ECL-650 (1), UO3), 12VDC
55
- **Exhaust Fan 7 Command (EF-7-C)**: BO (ECL-650 (2), UO1), 12VDC
56
- **Exhaust Fan 20 Command (EF-20-C)**: BO (ECL-650 (2), UO2), 12VDC
57
- **Pump 6 (Glycol Make-up) Command (P-6-C)**: BO (ECL-650 (2), UO3), 12VDC
58
- **Glycol Chilled Water Bypass Valve Output (CHWS-BYP-VLV1-O)**: AO (ECL-650 (1), UO4), 0-10VDC
59
- **Glycol Chilled Water Bypass Valve Output (GCHWP-BYP-O)**: AO (ECL-650 (2), UO4), 0-10VDC
60
61
### Software Points & Setpoints
62
- **Chiller 1 Differential Pressure Setpoint (CH-1-DP-SP)**: Setpoint (ECL-650 (1))
63
- **Chiller 2 Differential Pressure Setpoint (CH-2-DP-SP)**: Setpoint (ECL-650 (2))
64
- **Exhaust Fan 4 Failure (EF-4-FAIL)**: Alarm (ECL-650 (1))
65
- **Exhaust Fan 19 Failure (EF-19-FAIL)**: Alarm (ECL-650 (1))
66
- **Exhaust Fan 7 Failure (EF-7-FAIL)**: Alarm (ECL-650 (2))
67
- **Exhaust Fan 20 Failure (EF-20-FAIL)**: Alarm (ECL-650 (2))
68
- **Glycol Chilled Water Differential Pressure Setpoint (GCHW-DP-SP)**: Setpoint (Software)
69
- **Glycol System Normal Operating Pressure (GCHW-Press-SP)**: Setpoint (Software)
70
- **Glycol System Low-Low Pressure Alarm Limit (GCHW-Press-LOLMT)**: Setpoint (Software)
71
- **Glycol System High-High Pressure Alarm Limit (GCHW-Press-HILMT)**: Setpoint (Software)
72
- **Chilled Water Return Temp High Alarm (GCHWR-T-HILMT)**: Setpoint (Software) (e.g., SP+10°F)
73
- **Chilled Water Return Temp Low Alarm (GCHWR-T-LOLMT)**: Setpoint (Software) (e.g., SP-10°F)
74
75
---
76
77
## 3. Safety Devices & Interlocks
78
- **Glycol Pump Pressure Safety**: The glycol make-up pump will be de-energized if the system pressure drops below a low-low limit setpoint (`GCHW-Press-LOLMT`) or rises above a high-high limit setpoint (`GCHW-Press-HILMT`). An alarm is generated in both cases.
79
- **Glycol Pump Start Failure**: If a make-up pump is commanded ON (`P-3-C` or `P-6-C`) but its corresponding status contact (`P-3-S` or `P-6-S`) does not prove flow within a defined time, the pump command will be stopped and a malfunction alarm will be generated.
80
- **Glycol Tank Low Level**: If the glycol tank low level float switch (`GT-LL-A`) activates, the associated make-up pump will be stopped, and an alarm will be generated to prevent the pump from running dry.
81
82
---
83
84
## 4. Modes of Operation
85
86
### Chilled Water System Operation
87
- **Activation**: The chilled water pumps (`P-1`, `P-2`, `P-4`, `P-5`) and chillers are started **manually** for the cooling season.
88
- **Monitoring**: Once the system is active, the DDC controller monitors all associated points. All alarm functions become active.
89
- **Differential Pressure Control**:
90
- The `GCHW-DP` transmitter continuously measures the differential pressure across the supply and return mains.
91
- The controller modulates the normally open bypass valve (`CHWS-BYP-VLV1-O` / `GCHWP-BYP-O`) to maintain the `GCHW-DP-SP`.
92
- As system load increases (VAV boxes open), system DP will tend to drop, causing the bypass valve to modulate closed to force more flow out to the system.
93
- As system load decreases (VAV boxes close), system DP will tend to rise, causing the bypass valve to modulate open to relieve pressure.
94
95
### Glycol Make-up Pumps (Typical of P-3, P-6)
96
- **Monitoring**: The analog pressure transmitter in the expansion tank feed line is continuously monitored.
97
- **Pump Activation**:
98
- If system pressure drops below the `GCHW-Press-SP`, the corresponding make-up pump (`P-3-C` or `P-6-C`) is commanded **ON**.
99
- **Pump Deactivation**:
100
- The pump runs continuously until the system pressure rises to meet or exceed the `GCHW-Press-SP`. At this point, the pump is commanded **OFF**.
101
102
---
103
104
## 5. Alarms & Fault Conditions
105
All alarms shall be annunciated at the User workstation.
106
- **Pump Failure**:
107
- **Condition**: Status contact (`P-1-S`, `P-2-S`, etc.) indicates a pump is off when it should be running.
108
- **Priority**: High.
109
- **Loss of Chilled Water Flow**:
110
- **Condition**: The chilled water system flow switch (`FLOW-S`) opens while the system is expected to be active.
111
- **Priority**: High.
112
- **Chilled Water Temperature Out of Range**:
113
- **Condition**: The `GCHWS-T` or `GCHWR-T` reading exceeds the high (`GCHWR-T-HILMT`) or low (`GCHWR-T-LOLMT`) alarm limits.
114
- **Priority**: Medium.
115
- **Glycol Pump Pressure Alarm**:
116
- **Condition**: System pressure drops below `GCHW-Press-LOLMT` or rises above `GCHW-Press-HILMT`.
117
- **Priority**: High.
118
- **Glycol Pump Malfunction**:
119
- **Condition**: A make-up pump fails to prove status after being commanded ON.
120
- **Priority**: High.
121
- **Glycol Tank Low Level**:
122
- **Condition**: The low level float switch (`GT-LL-A`) is activated.
123
- **Priority**: Critical. Prevents pump operation.
124
- **Chiller Common Alarm**:
125
- **Condition**: The common alarm contact from either chiller (`CH-COM-A`) is activated.
126
- **Priority**: High.
127
128
---
129
130
## 6. Commissioning & Verification Checklist
131
- [ ] Verify that all pump status points (`P-1-S`, `P-2-S`, etc.) correctly report the ON/OFF status of each pump.
132
- [ ] With the system running, manually open the `FLOW-S` circuit and verify a "Loss of Chilled Water Flow" alarm is generated.
133
- [ ] Adjust the high and low alarm limits for `GCHWR-T` and verify that an alarm is generated when the temperature goes out of range.
134
- [ ] Verify the `GCHW-DP` reading is accurate. With the system running, manually adjust VAV box dampers and observe the `CHWS-BYP-VLV1-O` modulating to maintain the `GCHW-DP-SP`.
135
- [ ] Simulate a drop in system pressure and verify the correct glycol make-up pump (`P-3-C` or `P-6-C`) activates.
136
- [ ] Verify the make-up pump deactivates once the `GCHW-Press-SP` is achieved.
137
- [ ] Simulate a system pressure drop below `GCHW-Press-LOLMT` and verify the make-up pump is stopped and an alarm is generated.
138
- [ ] Simulate a system pressure rise above `GCHW-Press-HILMT` and verify the make-up pump is stopped and an alarm is generated.
139
- [ ] With a make-up pump commanded on, disconnect its status input (`P-3-S` or `P-6-S`) and verify a "Glycol Pump Malfunction" alarm is generated.
140
- [ ] Manually activate the `GT-LL-A` float switch and verify the make-up pump is de-energized and a "Glycol Tank Low Level" alarm is generated.
141
- [ ] Activate the `CH-COM-A` dry contact and verify a "Chiller Common Alarm" is generated.