Blame
|
1 | # Current Transducer - Quick Reference SSO |
||||||
| 2 | ||||||||
| 3 | **Device Type:** Analog Input - Current Sensor |
|||||||
| 4 | **Signal:** 0-10VDC / 4-20mA output |
|||||||
| 5 | **Power:** 24VAC/VDC (self-powered or loop-powered) |
|||||||
| 6 | **Version:** 1.0 | **Date:** Dec 2025 |
|||||||
| 7 | ||||||||
| 8 | --- |
|||||||
| 9 | ||||||||
| 10 | ## DEVICE OVERVIEW |
|||||||
| 11 | ||||||||
| 12 | **Common Models:** |
|||||||
| 13 | - Veris H8000 Series, CR Magnetics CR4395/CR5395, Functional Devices RIBX, Ohio Semitronics GW5, Wattnode WNC |
|||||||
| 14 | ||||||||
| 15 | **Used For:** |
|||||||
| 16 | Motor current monitoring, proof of operation, energy monitoring, fault detection, load verification, kW demand tracking |
|||||||
| 17 | ||||||||
| 18 | **Specifications:** |
|||||||
| 19 | - **Measurement:** AC current (amperage) |
|||||||
| 20 | - **Ranges:** Common ranges: |
|||||||
| 21 | * 0-5A, 0-10A, 0-20A, 0-50A, 0-100A, 0-200A, 0-500A |
|||||||
| 22 | * Select range for 150% of maximum expected load |
|||||||
| 23 | - **Technology:** Split-core CT (current transformer) - most common |
|||||||
| 24 | - **Output:** 0-10VDC or 4-20mA proportional to current |
|||||||
| 25 | - **Power:** 24VAC/VDC (externally powered) or loop-powered (4-20mA only) |
|||||||
| 26 | - **Wire Type:** 18AWG for signal output |
|||||||
| 27 | - **Accuracy:** ±1-2% of reading typical |
|||||||
| 28 | ||||||||
| 29 | **Environment:** 32-140°F, 0-95% RH non-condensing (indoor electrical rooms) |
|||||||
| 30 | ||||||||
| 31 | --- |
|||||||
| 32 | ||||||||
| 33 | ## SAFETY - PPE REQUIRED |
|||||||
| 34 | ||||||||
| 35 | - ☑ Safety glasses (ANSI Z87.1) |
|||||||
| 36 | - ☑ **Insulated gloves (Class 0 minimum for <1000V)** |
|||||||
| 37 | - ☑ **Arc-rated clothing (if working on energized equipment)** |
|||||||
| 38 | - ☑ Hard hat |
|||||||
| 39 | - ☑ Face shield (if working near exposed bus bars) |
|||||||
| 40 | ||||||||
| 41 | ### HAZARDS |
|||||||
| 42 | - ⚠️ **HIGH VOLTAGE - LETHAL** - Line voltage present (120V-480V typical) |
|||||||
| 43 | - ⚠️ **ARC FLASH HAZARD** - Can cause severe burns or death |
|||||||
| 44 | - ⚠️ **ENERGIZED CONDUCTORS** - Do not touch wires with CT installed |
|||||||
| 45 | - ⚠️ **MAGNETIC FIELDS** - Strong fields near high-current conductors |
|||||||
| 46 | ||||||||
| 47 | ### CRITICAL SAFETY RULES |
|||||||
| 48 | - ⚠️ **NEVER open CT secondary while CT installed on energized conductor** - Can generate lethal voltage |
|||||||
| 49 | - ⚠️ **NEVER install CT on energized conductor unless qualified** - Only qualified electricians |
|||||||
| 50 | - ⚠️ **CT must be closed before energizing** - Open CT can arc and fail |
|||||||
| 51 | ||||||||
| 52 | ### LOCKOUT/TAGOUT |
|||||||
| 53 | - [ ] **REQUIRED if installing on existing energized system** |
|||||||
| 54 | - [ ] **RECOMMENDED for all installations** - Safer to install with power off |
|||||||
| 55 | - [ ] Only qualified electricians should work on energized equipment |
|||||||
| 56 | - [ ] Arc flash hazard assessment required per NFPA 70E |
|||||||
| 57 | - [ ] If must work energized: Follow company arc flash procedures |
|||||||
| 58 | ||||||||
| 59 | ### QUALIFIED PERSONNEL ONLY |
|||||||
| 60 | **Installation of current transducers may require:** |
|||||||
| 61 | - Licensed electrician (check local codes) |
|||||||
| 62 | - Arc flash training and PPE |
|||||||
| 63 | - Electrical safety certification |
|||||||
| 64 | - Authorization to work on energized equipment |
|||||||
| 65 | ||||||||
| 66 | --- |
|||||||
| 67 | ||||||||
| 68 | ## INSTALLATION CHECKLIST |
|||||||
| 69 | ||||||||
| 70 | ### TOOLS NEEDED |
|||||||
| 71 | - Insulated tools (if working energized) |
|||||||
| 72 | - Wire strippers (18AWG) |
|||||||
| 73 | - Screwdrivers (insulated handles) |
|||||||
| 74 | - Multimeter (DMM) |
|||||||
| 75 | - Clamp meter (for verification) |
|||||||
| 76 | - Label maker |
|||||||
| 77 | - Voltage tester (non-contact) |
|||||||
| 78 | ||||||||
| 79 | ### MATERIALS |
|||||||
| 80 | - Current transducer (CT) - correct range for load |
|||||||
| 81 | - Control wiring (18AWG) |
|||||||
| 82 | - Wire nuts or terminal blocks |
|||||||
| 83 | - Cable ties (for CT support) |
|||||||
| 84 | - Labels (CT location and phase) |
|||||||
| 85 | ||||||||
| 86 | ### PRE-INSTALL |
|||||||
| 87 | - [ ] **CRITICAL:** Verify CT range ≥150% of maximum load current |
|||||||
| 88 | - [ ] **Confirm CT output type matches controller input (0-10V vs 4-20mA)** |
|||||||
| 89 | - [ ] Identify correct phase/conductor to monitor |
|||||||
| 90 | - [ ] Review electrical single-line diagram |
|||||||
| 91 | - [ ] Verify power locked out (if de-energized install) |
|||||||
| 92 | - [ ] Confirm qualified personnel available (if energized install) |
|||||||
| 93 | ||||||||
| 94 | ### INSTALL STEPS - SPLIT-CORE CT (Most Common) |
|||||||
| 95 | ||||||||
| 96 | **PREFERRED METHOD: DE-ENERGIZED INSTALLATION** |
|||||||
| 97 | ||||||||
| 98 | 1. **Lock out power:** |
|||||||
| 99 | - Coordinate with building operator |
|||||||
| 100 | - Lock circuit breaker in OFF position |
|||||||
| 101 | - Apply personal lock and tag |
|||||||
| 102 | - Verify zero voltage with meter |
|||||||
| 103 | - Wait for motor to stop completely |
|||||||
| 104 | ||||||||
| 105 | 2. **Select conductor:** |
|||||||
| 106 | - **Single phase:** Install CT on hot leg (L1) - NOT neutral |
|||||||
| 107 | - **Three phase:** Install CT on one phase (typically L1) |
|||||||
| 108 | - **For all three phases:** Need three CTs |
|||||||
| 109 | - **Verify conductor size** fits through CT opening |
|||||||
| 110 | ||||||||
| 111 | 3. **Install split-core CT:** |
|||||||
| 112 | - Open CT hinge (split-core opens like clamshell) |
|||||||
| 113 | - Position CT around conductor (centered) |
|||||||
| 114 | - **IMPORTANT: Arrow on CT points toward load** (away from source) |
|||||||
| 115 | - Close CT firmly until it clicks (secure latch) |
|||||||
| 116 | - **Do NOT force** - if won't close, verify no obstruction |
|||||||
| 117 | - Support CT with cable tie to prevent stress on conductor |
|||||||
| 118 | ||||||||
| 119 | 4. **Connect CT output wiring:** |
|||||||
| 120 | - **Self-powered (0-10V) - typically 3-wire:** |
|||||||
| 121 | * Red: +Power (24VAC/VDC from controller) |
|||||||
| 122 | * Black: Common |
|||||||
| 123 | * White/Green: Signal output (0-10V) |
|||||||
| 124 | - **Loop-powered (4-20mA) - typically 2-wire:** |
|||||||
| 125 | * Connect to controller 4-20mA input (polarity matters) |
|||||||
| 126 | * No external power required |
|||||||
| 127 | - Tighten terminals: 7-9 in-lbs |
|||||||
| 128 | - Route wiring away from high-voltage conductors |
|||||||
| 129 | ||||||||
| 130 | 5. **Label CT and wiring:** |
|||||||
| 131 | - CT label: "MOTOR-1-L1" (motor name and phase) |
|||||||
| 132 | - Arrow direction verified (toward load) |
|||||||
| 133 | - Wire labels at both ends |
|||||||
| 134 | ||||||||
| 135 | 6. **Restore power:** |
|||||||
| 136 | - Verify CT fully closed |
|||||||
| 137 | - Verify wiring secure |
|||||||
| 138 | - Remove personal lockout |
|||||||
| 139 | - Restore breaker to ON position |
|||||||
| 140 | ||||||||
| 141 | **ALTERNATE METHOD: ENERGIZED INSTALLATION (Qualified Personnel Only)** |
|||||||
| 142 | - Follow company arc flash procedures |
|||||||
| 143 | - Wear required arc-rated PPE |
|||||||
| 144 | - Use insulated tools only |
|||||||
| 145 | - Install CT while maintaining safe distance from exposed conductors |
|||||||
| 146 | - **NEVER open CT once installed on energized conductor** |
|||||||
| 147 | ||||||||
| 148 | ### POST-INSTALL |
|||||||
| 149 | - [ ] CT fully closed and latched |
|||||||
| 150 | - [ ] Arrow pointing toward load (verified) |
|||||||
| 151 | - [ ] CT positioned on correct phase |
|||||||
| 152 | - [ ] Wiring routed safely away from high-voltage |
|||||||
| 153 | - [ ] All terminals tight |
|||||||
| 154 | - [ ] Labels applied to CT and wiring |
|||||||
| 155 | - [ ] Power restored |
|||||||
| 156 | - [ ] Photos taken |
|||||||
| 157 | ||||||||
| 158 | --- |
|||||||
| 159 | ||||||||
| 160 | ## EXPECTED READINGS |
|||||||
| 161 | ||||||||
| 162 | ### PRE-POWER (Power OFF) |
|||||||
| 163 | - **CT Output:** Should read 0V or 4mA (no current flowing) |
|||||||
| 164 | - **CT Closed:** Verify CT fully latched (no gap) |
|||||||
| 165 | - **Wiring Continuity:** <5 ohms end-to-end |
|||||||
| 166 | ||||||||
| 167 | ### POWER-UP (Motor Running) |
|||||||
| 168 | ||||||||
| 169 | **For 0-10VDC Output:** |
|||||||
| 170 | | Motor Current | Typical Output (0-50A CT) | |
|||||||
| 171 | |--------------|---------------------------| |
|||||||
| 172 | | 0A (motor off) | 0V | |
|||||||
| 173 | | 10A | 2V | |
|||||||
| 174 | | 25A (mid-load) | 5V | |
|||||||
| 175 | | 50A (full load) | 10V | |
|||||||
| 176 | ||||||||
| 177 | **For 4-20mA Output:** |
|||||||
| 178 | | Motor Current | Typical Output (0-50A CT) | |
|||||||
| 179 | |--------------|---------------------------| |
|||||||
| 180 | | 0A (motor off) | 4mA | |
|||||||
| 181 | | 10A | 7.2mA | |
|||||||
| 182 | | 25A (mid-load) | 12mA | |
|||||||
| 183 | | 50A (full load) | 20mA | |
|||||||
| 184 | ||||||||
| 185 | **Motor Current Guidelines:** |
|||||||
| 186 | - **FLA (Full Load Amps):** On motor nameplate |
|||||||
| 187 | - **Starting current:** 5-8× FLA typical (brief inrush) |
|||||||
| 188 | - **Running current:** 70-100% FLA normal load |
|||||||
| 189 | - **No-load current:** 20-40% FLA typical |
|||||||
| 190 | - **Overcurrent:** >100% FLA indicates overload |
|||||||
| 191 | ||||||||
| 192 | ### VERIFICATION WITH CLAMP METER |
|||||||
| 193 | - Clamp actual conductor with clamp meter |
|||||||
| 194 | - Compare clamp meter reading to CT output |
|||||||
| 195 | - Calculate expected CT output: (Actual Current / CT Range) × Output Range |
|||||||
| 196 | - **Example:** 25A actual, 0-50A CT, 0-10V output: (25/50) × 10V = 5V expected |
|||||||
| 197 | - **Acceptable:** Within ±5% of calculated value |
|||||||
| 198 | ||||||||
| 199 | --- |
|||||||
| 200 | ||||||||
| 201 | ## PROOF OUT TESTS |
|||||||
| 202 | ||||||||
| 203 | ### TEST 1: Zero Current Check |
|||||||
| 204 | - **Do:** Motor off, measure CT output |
|||||||
| 205 | - **Expect:** |
|||||||
| 206 | * 0-10V output: 0-0.2V |
|||||||
| 207 | * 4-20mA output: 4-4.2mA |
|||||||
| 208 | - **Pass If:** Reading near zero (no current) |
|||||||
| 209 | ||||||||
| 210 | ### TEST 2: Motor Start/Stop Test |
|||||||
| 211 | - **Do:** Start motor, observe CT output change |
|||||||
| 212 | - **Expect:** |
|||||||
| 213 | * Reading increases from 0 to running current within 1-2 seconds |
|||||||
| 214 | * Brief spike during startup (5-8× normal) |
|||||||
| 215 | * Stabilizes at normal running current |
|||||||
| 216 | - **Pass If:** CT responds to motor starting |
|||||||
| 217 | ||||||||
| 218 | ### TEST 3: Current Reading Accuracy |
|||||||
| 219 | - **Do:** With motor running, compare CT to clamp meter |
|||||||
| 220 | - **Expect:** CT reading within ±5% of clamp meter |
|||||||
| 221 | - **Pass If:** Acceptable accuracy confirmed |
|||||||
| 222 | ||||||||
| 223 | ### TEST 4: Load Variation Test |
|||||||
| 224 | - **Do:** If load varies (VFD, dampers, valves), vary motor load |
|||||||
| 225 | - **Expect:** CT reading tracks load changes |
|||||||
| 226 | - **Pass If:** Output proportional to current |
|||||||
| 227 | ||||||||
| 228 | ### TEST 5: Three-Phase Balance (if all 3 phases monitored) |
|||||||
| 229 | - **Do:** Compare current on L1, L2, L3 |
|||||||
| 230 | - **Expect:** All three phases within ±10% of each other |
|||||||
| 231 | - **Pass If:** Balanced load (no phase loss) |
|||||||
| 232 | - **If unbalanced >10%:** Potential motor or wiring problem |
|||||||
| 233 | ||||||||
| 234 | ### TEST 6: Controller Integration |
|||||||
| 235 | - [ ] CT appears in controller AI list |
|||||||
| 236 | - [ ] Reading displays in Amps |
|||||||
| 237 | - [ ] Graphics show live current reading |
|||||||
| 238 | - [ ] Used for proof of operation or alarms |
|||||||
| 239 | - [ ] No faults or errors |
|||||||
| 240 | ||||||||
| 241 | --- |
|||||||
| 242 | ||||||||
| 243 | ## TROUBLESHOOTING |
|||||||
| 244 | ||||||||
| 245 | ### NO READING / ZERO OUTPUT |
|||||||
| 246 | 1. Verify motor is running (listen/observe) |
|||||||
| 247 | 2. Measure actual current with clamp meter - is there current? |
|||||||
| 248 | - **If no current:** Motor not running or power issue |
|||||||
| 249 | 3. Check CT closed and latched properly |
|||||||
| 250 | 4. Verify CT on correct conductor (not neutral) |
|||||||
| 251 | 5. Check CT arrow pointing toward load |
|||||||
| 252 | 6. For powered CT: Verify 24VAC/VDC supply voltage |
|||||||
| 253 | 7. Test CT output wiring continuity: <5 ohms |
|||||||
| 254 | 8. **If motor running with current but CT reads zero:** CT failed - replace |
|||||||
| 255 | ||||||||
| 256 | ### READING TOO LOW |
|||||||
| 257 | 1. Verify CT range adequate (not oversized) |
|||||||
| 258 | - Example: 10A load with 0-500A CT gives low resolution |
|||||||
| 259 | 2. Check CT fully closed (gap causes low reading) |
|||||||
| 260 | 3. Verify conductor centered in CT opening |
|||||||
| 261 | 4. Compare to clamp meter reading |
|||||||
| 262 | 5. Check for loose CT output wiring |
|||||||
| 263 | 6. **If consistently low by same %:** CT may need calibration |
|||||||
| 264 | ||||||||
| 265 | ### READING TOO HIGH |
|||||||
| 266 | 1. Verify CT range matches spec (not undersized) |
|||||||
| 267 | 2. Check CT arrow direction (reversed gives false reading) |
|||||||
| 268 | 3. Verify only ONE conductor through CT |
|||||||
| 269 | - **Common error:** Both hot and neutral = double reading |
|||||||
| 270 | 4. Compare to clamp meter |
|||||||
| 271 | 5. **If consistently high:** CT may be wrong ratio or failing |
|||||||
| 272 | ||||||||
| 273 | ### ERRATIC / FLUCTUATING READING |
|||||||
| 274 | 1. Check CT securely mounted (vibration can cause fluctuation) |
|||||||
| 275 | 2. Verify CT fully closed and latched |
|||||||
| 276 | 3. Check output wiring for loose connections |
|||||||
| 277 | 4. Look for EMI/RFI interference (route wiring away from power cables) |
|||||||
| 278 | 5. Verify good connection at controller input |
|||||||
| 279 | 6. **If motor has VFD:** Some fluctuation normal (PWM switching) |
|||||||
| 280 | ||||||||
| 281 | ### READING NEGATIVE |
|||||||
| 282 | 1. **CT arrow reversed** - pointing toward source instead of load |
|||||||
| 283 | 2. Open CT (if can be done safely) and reinstall with arrow toward load |
|||||||
| 284 | 3. **Or:** Some controllers allow signal reversal in software |
|||||||
| 285 | ||||||||
| 286 | ### HIGH INRUSH SPIKE CAUSES NUISANCE ALARMS |
|||||||
| 287 | 1. Normal motor startup is 5-8× FLA for 1-2 seconds |
|||||||
| 288 | 2. Adjust controller alarm time delay (3-5 seconds typical) |
|||||||
| 289 | 3. Or set alarm threshold higher (125% FLA instead of 110%) |
|||||||
| 290 | ||||||||
| 291 | ### CT WON'T CLOSE / GAP VISIBLE |
|||||||
| 292 | 1. Conductor too large for CT opening - need larger CT |
|||||||
| 293 | 2. Multiple conductors trying to fit through CT |
|||||||
| 294 | 3. CT hinge damaged - replace CT |
|||||||
| 295 | 4. Verify CT rated for conductor size |
|||||||
| 296 | ||||||||
| 297 | --- |
|||||||
| 298 | ||||||||
| 299 | ## ESCALATION - COMPLETE BEFORE CALLING |
|||||||
| 300 | ||||||||
| 301 | ### PRE-ESCALATION CHECKLIST |
|||||||
| 302 | - [ ] Verified motor is running (visual/audible confirmation) |
|||||||
| 303 | - [ ] Measured actual current with clamp meter |
|||||||
| 304 | - [ ] Verified CT fully closed and latched |
|||||||
| 305 | - [ ] Checked CT arrow pointing toward load |
|||||||
| 306 | - [ ] Verified only ONE conductor through CT |
|||||||
| 307 | - [ ] Verified correct conductor (not neutral) |
|||||||
| 308 | - [ ] Checked supply voltage for powered CT (24V ±10%) |
|||||||
| 309 | - [ ] Compared CT reading to clamp meter reading |
|||||||
| 310 | - [ ] Documented motor nameplate FLA |
|||||||
| 311 | - [ ] Taken photos of CT installation |
|||||||
| 312 | ||||||||
| 313 | ### PROVIDE THIS INFO |
|||||||
| 314 | - **CT:** [Mfg / Model / Range / Location] |
|||||||
| 315 | - **Motor:** [HP / Voltage / FLA from nameplate] |
|||||||
| 316 | - **CT Output Type:** 0-10V / 4-20mA |
|||||||
| 317 | - **CT Reading:** _____ A (from controller) |
|||||||
| 318 | - **Clamp Meter Reading:** _____ A (actual current) |
|||||||
| 319 | - **Motor Status:** Running / Off / Variable load |
|||||||
| 320 | - **CT Arrow Direction:** Toward load / Reversed / Unknown |
|||||||
| 321 | - **Supply Voltage (if powered):** _____ VAC/VDC |
|||||||
| 322 | - **Conductor:** L1 / L2 / L3 / Single phase |
|||||||
| 323 | - **Symptoms:** [Zero, low, high, erratic, negative] |
|||||||
| 324 | - **Steps Taken:** [Troubleshooting completed] |
|||||||
| 325 | ||||||||
| 326 | ### CONTACTS |
|||||||
| 327 | - **Field Specialist:** [Phone] |
|||||||
| 328 | - **Electrician:** [Phone] (if CT reinstall needed) |
|||||||
| 329 | - **Programmer:** [Phone] (if alarm/threshold issue) |
|||||||
| 330 | - **Dispatch:** [Phone] |
|||||||
| 331 | ||||||||
| 332 | --- |
|||||||
| 333 | ||||||||
| 334 | ## CALIBRATION |
|||||||
| 335 | ||||||||
| 336 | **When Needed:** |
|||||||
| 337 | - Rarely required - CTs are typically factory calibrated |
|||||||
| 338 | - If reading consistently off by >5% |
|||||||
| 339 | - After CT replacement |
|||||||
| 340 | ||||||||
| 341 | **Verification Procedure:** |
|||||||
| 342 | 1. Measure actual current with calibrated clamp meter |
|||||||
| 343 | 2. Record CT output from controller |
|||||||
| 344 | 3. Calculate expected output: (Actual Current / CT Range) × Output Range |
|||||||
| 345 | 4. Compare actual to expected |
|||||||
| 346 | 5. **If within ±5%:** No calibration needed |
|||||||
| 347 | 6. **If outside ±5%:** Apply controller offset or replace CT |
|||||||
| 348 | ||||||||
| 349 | **Controller Offset (if available):** |
|||||||
| 350 | - Most controllers allow calibration offset |
|||||||
| 351 | - Calculate correction factor |
|||||||
| 352 | - Apply in controller configuration |
|||||||
| 353 | - Retest with clamp meter |
|||||||
| 354 | ||||||||
| 355 | **Example:** |
|||||||
| 356 | - CT Range: 0-50A, Output: 0-10V |
|||||||
| 357 | - Clamp meter: 25A actual |
|||||||
| 358 | - Expected output: (25/50) × 10V = 5.0V |
|||||||
| 359 | - CT reads: 4.5V |
|||||||
| 360 | - Error: -0.5V (-10%) |
|||||||
| 361 | - Apply +0.5V offset in controller |
|||||||
| 362 | ||||||||
| 363 | **Acceptable Tolerance:** ±5% of reading |
|||||||
| 364 | ||||||||
| 365 | --- |
|||||||
| 366 | ||||||||
| 367 | ## COMMON ISSUES & TIPS |
|||||||
| 368 | ||||||||
| 369 | ✓ **CT sizing:** Select range for 150% of maximum expected current (allows for motor startup) |
|||||||
| 370 | ✓ **Arrow direction:** MUST point toward load (away from breaker) - reversed gives false readings |
|||||||
| 371 | ✓ **One conductor only:** Common error is running supply AND return through CT = 0 reading |
|||||||
| 372 | ✓ **Not on neutral:** Always install on hot leg, never neutral (neutral current should equal hot) |
|||||||
| 373 | ✓ **Three-phase motors:** Need three CTs for full monitoring (one per phase) |
|||||||
| 374 | ✓ **Single-phase motors:** One CT on hot leg sufficient |
|||||||
| 375 | ✓ **VFD applications:** CT must be rated for PWM waveforms (most modern CTs are) |
|||||||
| 376 | ✓ **Proof of operation:** Set alarm at 20-30% FLA (below normal running current) |
|||||||
| 377 | ✓ **Energy monitoring:** Sum all three phases for total power calculation (requires kW transducer) |
|||||||
| 378 | ✓ **Split-core advantage:** Can install without de-energizing (but only if qualified) |
|||||||
| 379 | ✓ **Solid-core CTs:** More accurate but require conductor disconnection for install |
|||||||
| 380 | ✓ **Startup inrush:** Normal 5-8× FLA spike for 1-2 seconds - don't set alarms too sensitive |
|||||||
| 381 | ||||||||
| 382 | ### Typical FLA by Motor HP (460V, 3-phase) |
|||||||
| 383 | *Note: These are typical values and can vary based on motor efficiency, manufacturer, and specific load conditions.* |
|||||||
| 384 | - 1 HP: 1.1A |
|||||||
| 385 | - 2 HP: 2.2A |
|||||||
| 386 | - 3 HP: 3.3A |
|||||||
| 387 | - 5 HP: 5.5A |
|||||||
| 388 | - 7.5 HP: 9A |
|||||||
| 389 | - 10 HP: 11A |
|||||||
| 390 | - 15 HP: 17A |
|||||||
| 391 | - 20 HP: 22A |
|||||||
| 392 | - 25 HP: 27A |
|||||||
| 393 | - 30 HP: 32A |
|||||||
| 394 | - 40 HP: 43A |
|||||||
| 395 | - 50 HP: 54A |
|||||||
| 396 | ||||||||
| 397 | --- |
|||||||
| 398 | ||||||||
| 399 | **Document ID:** SSO-CURRENT-001 |
|||||||
| 400 | **Revision:** 1.0 |
|||||||
| 401 | **Next Review:** Dec 2026 |
|||||||
| 402 | ||||||||
| 403 | **SAFETY WARNING:** Installation of current transducers involves work on or near energized electrical equipment. Only qualified personnel should perform this work. Always follow lockout/tagout procedures when possible. |
|||||||
