Blame

e0f744 root 2026-05-15 18:36:28
Add all documentation pages and update home index
1
# CO2 Sensor - Quick Reference SSO
2
3
**Device Type:** Analog Input - Gas Sensor
4
**Signal:** 0-10VDC / 4-20mA output
5
**Power:** 24VAC/VDC (powered transmitter)
6
**Version:** 1.0 | **Date:** Dec 2025
7
8
---
9
10
## DEVICE OVERVIEW
11
12
**Common Models:**
13
- Veris CWLSHTA, Telaire T8000 Series, Johnson Controls GMP/GMW, Siemens QPA2000, BAPI BA/CO2
14
15
**Used For:**
16
Demand control ventilation (DCV), indoor air quality monitoring, occupancy detection, energy savings
17
18
**Specifications:**
19
- **Range:** 0-2000 PPM typical (0-5000 PPM for high-occupancy)
20
- **Accuracy:** ±50 PPM typical
21
- **Technology:** Non-dispersive infrared (NDIR) - most common
22
- **Output:** 0-10VDC or 4-20mA proportional to CO2 level
23
- **Power:** 24VAC or 24VDC, 15-50mA consumption
24
- **Wire Type:** 18AWG minimum, shielded recommended for long runs
25
- **Wiring:** 3-wire (power, common, signal output)
26
27
**Environment:** 32-122°F, 0-95% RH non-condensing (indoor only)
28
29
---
30
31
## SAFETY - PPE REQUIRED
32
33
- ☑ Safety glasses (ANSI Z87.1)
34
- ☑ Work gloves
35
- ☑ Hard hat (if overhead work)
36
- ☑ Ladder safety equipment (if >6 feet)
37
38
### HAZARDS
39
- **LADDER WORK** - Most common hazard (sensors typically mounted high)
40
- **ELECTRICAL** - 24VAC/VDC low voltage (low shock hazard, but always exercise caution)
41
- **CONFINED SPACES** - Some mechanical room installations
42
43
### LOCKOUT/TAGOUT
44
- [ ] **NOT required** - low voltage device
45
- [ ] Notify building occupants if working in occupied space
46
47
---
48
49
## INSTALLATION CHECKLIST
50
51
### TOOLS NEEDED
52
- Drill + bits
53
- Wire strippers (18AWG)
54
- Screwdrivers
55
- Multimeter (DMM)
56
- Level
57
- Tape measure
58
- Label maker
59
- Ladder (appropriate height)
60
61
### PRE-INSTALL
62
- [ ] Location per blueprints (typically 4-6 feet above floor)
63
- [ ] Avoid locations near:
64
* Doors or windows (outside air infiltration)
65
* Supply diffusers (dilutes reading)
66
* Kitchen/break room areas (cooking affects reading)
67
* Smoking areas or loading docks
68
- [ ] Verify sensor range matches application (0-2000 vs 0-5000 PPM)
69
- [ ] Confirm sensor type matches controller input (0-10V vs 4-20mA)
70
71
### INSTALL STEPS
72
1. **Mount sensor:**
73
- Height: 4-6 feet above floor (breathing zone)
74
- Representative location (not corner or dead air space)
75
- Use level to ensure horizontal
76
- Wall mount or electrical box
77
78
2. **Route and terminate wiring:**
79
- **3-Wire Standard:**
80
* Red: +24VAC/VDC power
81
* Black: Common
82
* White/Green: Signal output (0-10V or 4-20mA)
83
- Tighten terminals: 7-9 in-lbs
84
- Support wire, leave 12" service loop
85
86
3. **Label wiring:**
87
- Example: "RM-201-CO2" or "AHU-1-RA-CO2"
88
- Label both ends
89
90
### POST-INSTALL
91
- [ ] Sensor mounted securely and level
92
- [ ] Height 4-6 feet above floor
93
- [ ] Location representative of space
94
- [ ] All wires terminated tight
95
- [ ] Labels applied both ends
96
- [ ] Work area cleaned
97
- [ ] Photos taken
98
99
---
100
101
## EXPECTED READINGS
102
103
### PRE-POWER (Power OFF)
104
- **Continuity:** Each wire <5 ohms end-to-end
105
- **Isolation:** >10K ohms to ground
106
107
### POWER-UP
108
- **Supply Voltage:** 24VAC/VDC ±10% (21.6-26.4V)
109
- **Power Consumption:** 15-50mA typical
110
- **Warm-up Time:** 5-30 minutes (NDIR sensors need stabilization)
111
112
### NORMAL READINGS
113
| CO2 Level | Condition | 0-10V Output | 4-20mA Output |
114
| --------- | ------------------- | ------------ | ------------- |
115
| 400 PPM | Outdoor air | 2.0V | 7.2mA |
116
| 600 PPM | Low occupancy | 3.0V | 9.6mA |
117
| 800 PPM | Normal occupancy | 4.0V | 12.0mA |
118
| 1000 PPM | High occupancy | 5.0V | 14.4mA |
119
| 1200 PPM | Very high occupancy | 6.0V | 16.8mA |
120
121
**Typical Indoor Range:** 400-1200 PPM
122
**Outdoor Fresh Air:** ~400-450 PPM
123
**ASHRAE Max Recommended:** 1000 PPM (for comfort)
124
**Code Max (some jurisdictions):** 1200 PPM
125
126
---
127
128
## PROOF OUT TESTS
129
130
### TEST 1: Warm-Up Period
131
- **Do:** Power sensor and wait 5-30 minutes
132
- **Expect:** Reading stabilizes (initial reading may be high or low)
133
- **Pass If:** Reading stable within 30 minutes
134
135
### TEST 2: Fresh Air Test
136
- **Do:** Hold sensor near outside air intake or open window
137
- **Expect:** Reading drops to ~400-500 PPM (outdoor air level)
138
- **Pass If:** Reading drops and stabilizes at outdoor level
139
140
### TEST 3: Breath Test (Occupancy Simulation)
141
- **Do:** Exhale breath directly at sensor from 6-12 inches away for 10 seconds
142
- **Expect:** Reading increases 200-400 PPM within 30-60 seconds
143
- **Pass If:** Reading increases then gradually returns to baseline
144
145
### TEST 4: Range Test
146
- **Do:** Compare occupied space reading to unoccupied/ventilated reading
147
- **Expect:**
148
* Unoccupied with ventilation: 400-600 PPM
149
* Occupied space: 600-1200 PPM depending on density
150
- **Pass If:** Readings make sense for conditions
151
152
### TEST 5: Controller Integration
153
- [ ] Sensor appears in controller AI list
154
- [ ] Reading displays in PPM
155
- [ ] Graphics show live data
156
- [ ] Controller uses reading for DCV control
157
- [ ] No faults or errors
158
159
---
160
161
## TROUBLESHOOTING
162
163
### NO READING / SENSOR FAULT
164
1. Verify supply voltage at sensor: 24VAC/VDC ±10%
165
2. Wait 30 minutes for warm-up period
166
3. Check all wiring connections tight
167
4. Test continuity end-to-end: <5 ohms
168
5. Measure output signal: Should be 2-10V or 4-20mA (not 0V or 0mA)
169
6. **If 0V or 0mA:** Sensor failed - replace
170
7. **If voltage present but no reading:** Check controller input config
171
172
### READING STUCK / NOT CHANGING
173
1. Verify sensor has power (LED indicator if equipped)
174
2. Wait for warm-up period (30 min)
175
3. Perform breath test - should increase reading
176
4. Check sensor lens/opening not obstructed or dirty
177
5. **If still stuck:** Replace sensor (NDIR element failed)
178
179
### READING TOO HIGH (Always >1000 PPM)
180
1. Check sensor location:
181
- Near kitchen or break room?
182
- In dead air space with poor circulation?
183
- Too close to occupants?
184
2. Verify outdoor air ventilation operating correctly
185
3. Compare to portable CO2 meter (calibrated reference)
186
4. **If consistently high by same offset:** Calibrate sensor
187
5. **If true high reading:** Increase ventilation rate
188
189
### READING TOO LOW (Always <400 PPM)
190
1. Check sensor location - too close to OA intake or supply diffuser?
191
2. Verify sensor not in high-velocity airstream
192
3. Compare to portable CO2 meter
193
4. **If sensor reads low:** Calibrate or replace
194
5. **Note:** Reading below 400 PPM indoors is usually sensor error
195
196
### ERRATIC / FLUCTUATING READINGS
197
1. Check for air currents affecting sensor (supply diffuser too close)
198
2. Verify sensor mounted securely (not vibrating)
199
3. Check wiring for EMI/RFI interference
200
4. Look for moisture in sensor or connections
201
5. **If persists:** Replace sensor
202
203
### SLOW RESPONSE
204
1. Normal: CO2 sensors respond slower than temperature (1-2 min typical)
205
2. Check sensor sampling rate (some have adjustable averaging)
206
3. Verify sensor not obstructed
207
4. **If >5 minutes to respond:** Sensor may be failing - replace
208
209
---
210
211
## ESCALATION - COMPLETE BEFORE CALLING
212
213
### PRE-ESCALATION CHECKLIST
214
- [ ] Verified supply voltage at sensor (24V ±10%)
215
- [ ] Waited 30+ minutes for warm-up period
216
- [ ] Verified all wiring connections
217
- [ ] Performed breath test (reading should increase)
218
- [ ] Compared to portable CO2 meter (if available)
219
- [ ] Checked sensor location (away from influences)
220
- [ ] Documented readings over 30+ minute period
221
- [ ] Taken photos of installation and location
222
223
### PROVIDE THIS INFO
224
- **Sensor:** [Mfg / Model / Range / Location]
225
- **Supply Voltage:** _____ VAC/VDC
226
- **Output Signal:** 0-10V or 4-20mA
227
- **Current Reading:** _____ PPM
228
- **Reference Reading:** _____ PPM (if available)
229
- **Space Occupancy:** Occupied / Unoccupied / # people
230
- **Ventilation Status:** OA damper position ____ %
231
- **Symptoms:** [Stuck, erratic, high, low, no reading]
232
- **Response to Breath Test:** [Increased / No change]
233
- **Steps Taken:** [Troubleshooting completed]
234
235
### CONTACTS
236
- **Field Specialist:** [Phone]
237
- **Programmer:** [Phone] (if DCV sequence issue)
238
- **Project Manager:** [Phone]
239
- **Dispatch:** [Phone]
240
241
---
242
243
## CALIBRATION
244
245
**When Needed:**
246
- Annual calibration recommended (NDIR sensors drift over time)
247
- After sensor replacement
248
- If reading consistently off by >100 PPM
249
250
**Methods:**
251
252
**OPTION A: Fresh Air Calibration (Simple)**
253
1. Expose sensor to outdoor air for 20+ minutes
254
2. Outdoor air should read 400-450 PPM
255
3. Adjust sensor calibration to 400 PPM (if adjustable)
256
4. **Note:** Only accurate if outdoor air is actually ~400 PPM
257
258
**OPTION B: Zero Gas Calibration (Accurate)**
259
1. Requires calibration gas (400 PPM CO2 in nitrogen)
260
2. Apply calibration gas to sensor per manufacturer procedure
261
3. Adjust sensor to match calibration gas concentration
262
4. **Preferred method** - most accurate
263
264
**OPTION C: Controller Offset (Temporary)**
265
1. If sensor consistently off by fixed amount (e.g., always reads 100 PPM high)
266
2. Apply offset in controller configuration
267
3. **Not a permanent fix** - sensor should be recalibrated or replaced
268
269
**Acceptable Tolerance:** ±50 PPM
270
271
**Document:** Tech name, date, calibration method, before/after readings
272
273
---
274
275
## COMMON ISSUES & TIPS
276
277
**Mount height:** 4-6 feet (breathing zone) - CO2 heavier than air but well-mixed indoors
278
**Warm-up time:** Always allow 30 min minimum after power-up before commissioning
279
**Location critical:** Representative location essential - avoid OA intakes and supply diffusers
280
**NDIR technology:** Most accurate but requires annual calibration
281
**Range selection:** 0-2000 PPM for most spaces, 0-5000 PPM for high-occupancy (auditoriums, gyms)
282
**DCV savings:** Typically 10-30% energy savings vs fixed ventilation rate
283
**ASHRAE 62.1:** Requires CO2 sensors for DCV in densely occupied spaces
284
**Breath test:** Quick field verification - exhaled breath ~40,000 PPM CO2
285
**Outdoor air:** ~400-450 PPM baseline (slowly increasing globally ~2 PPM/year)
286
**False high readings:** Check for nearby combustion sources, kitchens, smoking
287
**Multi-zone systems:** One sensor per zone typical, or duct-mounted in return air
288
289
---
290
291
**Document ID:** SSO-CO2-001
292
**Revision:** 1.0
293
**Next Review:** Dec 2026