Flow Switch - Quick Reference SSO
Device Type: Binary Input - Flow Detection
Signal: Dry contact (NO or NC)
Power: Unpowered (mechanical switch) or 24VAC (relay type)
Version: 1.0 | Date: Dec 2025
DEVICE OVERVIEW
Common Models:
- McDonnell Miller FS4-3/FS7, Cleveland Controls AFS, Dwyer WFS/SFS, Gems FS-200, Johnson Controls F61/F63
Used For:
Proof of water flow (chilled water, hot water, condenser water), pump status verification, freeze protection, low flow alarm, interlock safety
Technologies:
- Paddle Type: Mechanical paddle in pipe flow, contact closes when flow pushes paddle
- Thermal Dispersion: Heater element, flow cools element, triggers switch
- Target (Vane) Type: Spring-loaded target, flow overcomes spring, closes contact
- Differential Pressure: Measures ΔP across orifice, switch triggers at setpoint
Specifications:
- Pipe Sizes: 1/2” to 12” (varies by model)
- Flow Range: 0.3-10 ft/sec typical (consult manufacturer)
- Setpoint: Adjustable (gpm or ft/sec)
- Contact Type: SPDT typical (NO, NC, COM)
- Contact Rating: 1-5A at 24-250VAC
- Connection: NPT threaded (1/2”, 3/4”, 1”) or flange mount
- Material: Brass, stainless steel, or plastic (application dependent)
Environment: Varies by liquid type (water, glycol, oil)
SAFETY - PPE REQUIRED
- ☑ Safety glasses (ANSI Z87.1)
- ☑ Heat-resistant gloves (pipes may be hot or cold)
- ☑ Face shield (if system under pressure)
- ☑ Chemical-resistant gloves (if glycol or chemicals)
HAZARDS
- ⚠️ PRESSURIZED SYSTEM - Water systems under 30-150 PSI
- ⚠️ HOT WATER - Up to 200°F in heating systems
- ⚠️ COLD WATER - 35-45°F in chilled water (cold burns from prolonged contact)
- ⚠️ CHEMICAL EXPOSURE - Glycol, water treatment chemicals (if leak)
- ⚠️ WATER DAMAGE - Improper installation causes leaks
SYSTEM ISOLATION REQUIRED
- MANDATORY: Close isolation valves upstream and downstream
- Drain system pressure in section being worked
- Verify 0 PSI with pressure gauge before opening pipe
- Keep bucket/absorbent ready for residual water
COORDINATION
- Notify building operator of system shutdown
- Coordinate with mechanical contractor or plumber
- Plan work during off-hours if possible (minimizes impact)
- Verify bypass valves available (if equipped)
INSTALLATION CHECKLIST
TOOLS NEEDED
- Pipe wrenches (two - for installation and backup)
- Teflon tape or pipe dope
- Drill + bits (for paddle insertion hole)
- Hacksaw or tubing cutter (if modifying pipe)
- Wire strippers (18AWG)
- Multimeter
- Bucket and rags (for water drainage)
- Pressure gauge (verify 0 PSI)
- Label maker
MATERIALS
- Flow switch (correct pipe size and flow range)
- Pipe fittings (if needed: Tee, nipples, unions)
- Teflon tape or pipe thread sealant
- Isolation valves (if not present)
- Wire (18AWG)
- Wire nuts or terminal blocks
- Ball valve or drain (for testing)
PRE-INSTALL
- Verify flow switch rated for:
- Pipe size (must match)
- Flow range (gpm expected)
- Liquid type (water, glycol, oil)
- Temperature range
- Pressure rating
- Identify installation location:
- Straight pipe section (10× pipe diameter from elbows/valves)
- Accessible for service
- After pump (in flow direction)
- Verify isolation valves present or plan to install
INSTALL STEPS - PADDLE TYPE (Most Common)
STEP 1: System Isolation
- Notify building operator
- Close isolation valves upstream and downstream
- Open drain valve to depressurize section
- Verify 0 PSI with pressure gauge
- Place bucket under work area
STEP 2: Prepare Pipe
OPTION A: Existing Tee/Boss (Preferred)
- Use existing threaded opening in pipe
- Clean threads and apply Teflon tape
OPTION B: Install New Tee (Requires Pipe Modification)
- Cut pipe at selected location
- Install Tee fitting with unions for future service
- Ensure Tee points in flow direction (arrow on switch)
- Pressure test before proceeding
OPTION C: Hot Tap (Specialized, Requires Contractor)
- Specialized procedure for drilling a hole in a live, pressurized pipe (requires highly specialized equipment and training)
- Typically requires mechanical contractor with hot tapping expertise
- Used when system cannot be drained or taken offline
- CRITICAL SAFETY: Only qualified, experienced personnel with proper safety protocols should perform hot tapping.
STEP 3: Install Flow Switch
- Apply Teflon tape to switch threads (3-4 wraps, clockwise)
- Or use pipe dope per manufacturer
- Thread switch into Tee or boss
- Orient switch:
- Arrow on switch points in flow direction (critical)
- Electrical connection accessible for wiring
- Paddle perpendicular to flow (not parallel)
- Tighten switch:
- Hand tight, then 1-2 turns with wrench
- Do not overtighten - can crack housing
- Verify paddle moves freely:
- Gently push paddle (if accessible)
- Should return to rest position
STEP 4: Set Flow Setpoint
- Adjustable models:
- Rotate adjustment dial to desired flow rate (gpm or ft/sec)
- Typical setting: 1-2 ft/sec for proof of flow
- Consult pump curve for expected flow
- Fixed models:
- Verify setpoint adequate for application
- Typically 0.5-1.0 ft/sec factory set
STEP 5: Wire Flow Switch
- Locate terminal compartment on switch
- Remove cover (may require screwdriver)
- Identify terminals:
- COM (Common)
- NO (Normally Open) - Closes when flow present
- NC (Normally Closed) - Opens when flow present
- Connect to controller:
- Use NO contact for proof of flow:
- NO → Controller BI
- COM → Controller COM
- Flow present = Contact closed = TRUE/1
- No flow = Contact open = FALSE/0
- Use NO contact for proof of flow:
- Tighten terminal screws: 7-9 in-lbs
- Route wiring away from hot pipes
- Reinstall terminal cover (weatherproof seal)
STEP 6: Pressure Test and Restore
- Close all drain valves
- Slowly open isolation valves:
- Open upstream valve 1/4 turn, check for leaks
- If no leaks, fully open upstream valve
- Repeat for downstream valve
- Check for leaks at switch installation
- Tighten if minor seepage (1/4 turn max)
- If significant leak: Close valves, remove switch, reapply sealant
- Verify system pressure normal (30-150 PSI typical)
- Start pump (coordinate with operator)
STEP 7: Label
- Example: “PUMP-1-FLOW” or “CHW-FLOW”
- Label at both switch and controller
POST-INSTALL
- Flow switch installed with arrow in flow direction
- No leaks at installation (verified under pressure)
- Setpoint configured appropriately
- Wiring terminated tight
- Terminal cover reinstalled (weatherproof)
- Labels applied
- System pressure normal
- Photos taken
EXPECTED READINGS
NO FLOW (Pump OFF or Valves Closed)
- Contact State: Open (NO) or Closed (NC)
- Controller Reading: FALSE/0 (using NO contact)
- Paddle Position: At rest (spring returns paddle)
FLOW PRESENT (Pump Running, Normal Flow)
- Contact State: Closed (NO) or Open (NC)
- Controller Reading: TRUE/1 (using NO contact)
- Paddle Position: Deflected by flow (overcoming spring)
- Typical Flow: 2-8 ft/sec in HVAC piping
FLOW SETPOINT
- Proof of Flow: 0.5-1.5 ft/sec (low setpoint, confirms pump running)
- Minimum Flow Alarm: 1.5-3.0 ft/sec (detects low flow condition)
- Target Flow: 3-8 ft/sec typical for HVAC (consult pump curve)
PROOF OUT TESTS
TEST 1: No Flow Test
- Do: Pump off, valves closed, no flow
- Expect:
- Contact open (NO) = FALSE
- Controller shows “No Flow”
- Pass If: Switch correctly shows no flow
TEST 2: Flow Established Test
- Do: Start pump, establish flow
- Expect:
- Contact closes (NO) within 2-5 seconds
- Controller changes to “Flow” or TRUE/1
- Pump current increases (verify with clamp meter)
- Pass If: Switch detects flow when pump starts
TEST 3: Flow Stoppage Test
- Do: Close downstream valve (simulate flow stoppage)
- WARNING: Don’t leave valve closed long (pump deadhead)
- Expect:
- Contact opens (NO) = FALSE after 2-5 seconds
- Controller shows “No Flow” alarm
- Pass If: Switch detects loss of flow
- Immediately: Reopen valve after test
TEST 4: Minimum Flow Test
- Do: Throttle flow with valve to minimum
- Expect: Switch triggers at setpoint flow rate
- Pass If: Triggers appropriately at setpoint
TEST 5: Leak Test
- Do: Inspect all connections under full pressure
- Expect: No water seepage or leaks
- Pass If: Completely dry after 30 minutes operation
TEST 6: Integration with BAS
- Switch appears in controller BI list
- Flow/no-flow status displays correctly
- Graphics show flow status
- Pump interlock logic works (alarm if pump on but no flow)
- No communication errors
TROUBLESHOOTING
FLOW SWITCH NEVER SHOWS FLOW (Always FALSE)
- Verify pump is running:
- Check pump current with clamp meter
- Hear pump motor running
- If pump not running: Pump problem, not switch
- Check for actual flow:
- Feel pipe vibration (flow present)
- Check pressure gauges (ΔP indicates flow)
- If no flow with pump running: Closed valve, air lock, or pump issue
- Check flow switch orientation:
- Arrow must point in flow direction
- If reversed: Flow pushes paddle closed (wrong way)
- Check setpoint:
- May be set too high for actual flow
- Reduce setpoint and retest
- Check paddle:
- Paddle may be stuck or broken
- Remove switch (isolate system first), inspect paddle
- Test contact:
- Manually push paddle, measure contact continuity
- If no continuity when paddle pushed: Switch failed
FLOW SWITCH ALWAYS SHOWS FLOW (Always TRUE)
- Check for actual flow:
- Pump may be running (expected)
- If pump off but shows flow: False reading
- Check wiring:
- NC contact may be wired instead of NO
- Wires may be crossed or shorted
- Test contact:
- Disconnect wiring, measure contact with no flow
- If contact closed with no flow: Switch failed or stuck
ERRATIC FLOW INDICATION (Cycling TRUE/FALSE)
- Air in system:
- Air pockets cause intermittent paddle deflection
- Vent system to remove air
- Turbulent flow:
- Switch too close to elbow, valve, or pump
- Relocate to straight section (10× pipe diameter)
- Vibration:
- Pipe vibration causing paddle to flutter
- Secure piping to reduce vibration
- Increase switch time delay (if adjustable)
- Flow oscillation:
- Pump cycling or VFD hunting
- Check pump and control system
LEAKING AT FLOW SWITCH
- Minor seepage:
- Tighten switch 1/4 turn
- Do not overtighten (can crack housing)
- Persistent leak:
- Remove switch, inspect threads
- Reapply Teflon tape (3-4 wraps) or pipe dope
- Inspect O-ring or gasket (replace if damaged)
- Reinstall and pressure test
- Crack in housing:
- Replace switch (overtightened or defective)
DELAYED RESPONSE (Slow to Show Flow)
- Normal delay: 2-5 seconds typical for paddle to deflect
- Check setpoint: May be set too high, paddle struggles to reach
- Check paddle: May be corroded or sticky
- Remove and clean (isolate system first)
- Reduce setpoint: If flow low, lower setpoint to 0.5 ft/sec
FALSE FLOW INDICATION (Shows Flow with No Pump)
- Gravity flow:
- System on multiple levels, gravity flow possible
- Install check valve to prevent reverse flow
- Paddle stuck:
- Debris or corrosion holding paddle deflected
- Remove switch, clean paddle, reinstall
- Contact stuck closed:
- Switch failed, replace
ESCALATION - COMPLETE BEFORE CALLING
PRE-ESCALATION CHECKLIST
- Verified pump actually running (current measurement)
- Verified flow present (pipe vibration, pressure gauges)
- Checked flow switch arrow points in flow direction
- Tested contact manually (paddle pushed = contact change)
- Verified wiring connections tight
- Checked for leaks at installation
- Inspected paddle for damage or obstruction
- Documented setpoint setting
- Taken photos of installation and orientation
PROVIDE THIS INFO
- Flow Switch: [Mfg / Model / Pipe Size / Location]
- Application: CHW / HW / Condenser water / Other
- Pump Status: Running / Off / Variable speed ____%
- Pump Current: _____ A (measured with clamp meter)
- Flow Expected: _____ gpm (from pump curve)
- Setpoint: _____ ft/sec or gpm
- Arrow Direction: Verified in flow direction / Wrong / Unsure
- Contact Status: Open / Closed / _____ ohms
- Pressure: _____ PSI (supply) | _____ PSI (return) | ΔP _____ PSI
- Symptoms: [Never shows flow, always shows flow, erratic, leaking]
- Steps Taken: [Troubleshooting completed]
CONTACTS
- Field Specialist: [Phone]
- Plumber/Mechanical Contractor: [Phone] (if leak or system issue)
- Programmer: [Phone] (if interlock logic issue)
- Dispatch: [Phone]
COMMON ISSUES & TIPS
✓ Arrow direction CRITICAL: Must point in flow direction or won’t work
✓ Straight pipe required: Install 10× pipe diameter from elbows, valves, pumps
✓ Setpoint selection: 0.5-1.5 ft/sec for proof of flow, higher for minimum flow alarm
✓ Pipe size matters: Must match pipe size or flow velocity calculation wrong
✓ Air in system: Most common cause of erratic behavior - vent system
✓ Teflon tape application: 3-4 wraps clockwise, don’t overtighten switch
✓ No flow with pump running: Check for closed valves, air lock, pump cavitation
✓ Proof of operation: Use in interlock: “Alarm if pump ON but no flow >60 seconds”
✓ Freeze protection: “Alarm if temperature <40°F AND no flow”
✓ Low flow alarm: Set higher setpoint (3-5 ft/sec) to detect loss of flow
✓ Pressure vs flow: Pressure can be normal with no flow (closed valve) - flow switch needed
✓ Time delay: Add 30-60 second delay in controller to prevent nuisance alarms at startup
Typical Flow Velocities (HVAC Systems)
- Chilled Water: 4-8 ft/sec
- Hot Water: 2-6 ft/sec
- Condenser Water: 5-10 ft/sec
- Glycol (20%): 3-6 ft/sec
- Proof of Flow Setting: 0.5-1.5 ft/sec (20-30% of target)
Document ID: SSO-FLOW-SWITCH-001
Revision: 1.0
Next Review: Dec 2026
SAFETY WARNING: Flow switch installation requires system isolation and draining. Coordinate with building operations and mechanical contractor. Improper installation can cause leaks and water damage.