CO2 Sensor - Quick Reference SSO
Device Type: Analog Input - Gas Sensor
Signal: 0-10VDC / 4-20mA output
Power: 24VAC/VDC (powered transmitter)
Version: 1.0 | Date: Dec 2025
DEVICE OVERVIEW
Common Models:
- Veris CWLSHTA, Telaire T8000 Series, Johnson Controls GMP/GMW, Siemens QPA2000, BAPI BA/CO2
Used For:
Demand control ventilation (DCV), indoor air quality monitoring, occupancy detection, energy savings
Specifications:
- Range: 0-2000 PPM typical (0-5000 PPM for high-occupancy)
- Accuracy: ±50 PPM typical
- Technology: Non-dispersive infrared (NDIR) - most common
- Output: 0-10VDC or 4-20mA proportional to CO2 level
- Power: 24VAC or 24VDC, 15-50mA consumption
- Wire Type: 18AWG minimum, shielded recommended for long runs
- Wiring: 3-wire (power, common, signal output)
Environment: 32-122°F, 0-95% RH non-condensing (indoor only)
SAFETY - PPE REQUIRED
- ☑ Safety glasses (ANSI Z87.1)
- ☑ Work gloves
- ☑ Hard hat (if overhead work)
- ☑ Ladder safety equipment (if >6 feet)
HAZARDS
- ⚠ LADDER WORK - Most common hazard (sensors typically mounted high)
- ⚠ ELECTRICAL - 24VAC/VDC low voltage (low shock hazard, but always exercise caution)
- ⚠ CONFINED SPACES - Some mechanical room installations
LOCKOUT/TAGOUT
- NOT required - low voltage device
- Notify building occupants if working in occupied space
INSTALLATION CHECKLIST
TOOLS NEEDED
- Drill + bits
- Wire strippers (18AWG)
- Screwdrivers
- Multimeter (DMM)
- Level
- Tape measure
- Label maker
- Ladder (appropriate height)
PRE-INSTALL
- Location per blueprints (typically 4-6 feet above floor)
- Avoid locations near:
- Doors or windows (outside air infiltration)
- Supply diffusers (dilutes reading)
- Kitchen/break room areas (cooking affects reading)
- Smoking areas or loading docks
- Verify sensor range matches application (0-2000 vs 0-5000 PPM)
- Confirm sensor type matches controller input (0-10V vs 4-20mA)
INSTALL STEPS
-
Mount sensor:
- Height: 4-6 feet above floor (breathing zone)
- Representative location (not corner or dead air space)
- Use level to ensure horizontal
- Wall mount or electrical box
-
Route and terminate wiring:
- 3-Wire Standard:
- Red: +24VAC/VDC power
- Black: Common
- White/Green: Signal output (0-10V or 4-20mA)
- Tighten terminals: 7-9 in-lbs
- Support wire, leave 12” service loop
- 3-Wire Standard:
-
Label wiring:
- Example: “RM-201-CO2” or “AHU-1-RA-CO2”
- Label both ends
POST-INSTALL
- Sensor mounted securely and level
- Height 4-6 feet above floor
- Location representative of space
- All wires terminated tight
- Labels applied both ends
- Work area cleaned
- Photos taken
EXPECTED READINGS
PRE-POWER (Power OFF)
- Continuity: Each wire <5 ohms end-to-end
- Isolation: >10K ohms to ground
POWER-UP
- Supply Voltage: 24VAC/VDC ±10% (21.6-26.4V)
- Power Consumption: 15-50mA typical
- Warm-up Time: 5-30 minutes (NDIR sensors need stabilization)
NORMAL READINGS
| CO2 Level | Condition | 0-10V Output | 4-20mA Output |
|---|---|---|---|
| 400 PPM | Outdoor air | 2.0V | 7.2mA |
| 600 PPM | Low occupancy | 3.0V | 9.6mA |
| 800 PPM | Normal occupancy | 4.0V | 12.0mA |
| 1000 PPM | High occupancy | 5.0V | 14.4mA |
| 1200 PPM | Very high occupancy | 6.0V | 16.8mA |
Typical Indoor Range: 400-1200 PPM
Outdoor Fresh Air: ~400-450 PPM
ASHRAE Max Recommended: 1000 PPM (for comfort)
Code Max (some jurisdictions): 1200 PPM
PROOF OUT TESTS
TEST 1: Warm-Up Period
- Do: Power sensor and wait 5-30 minutes
- Expect: Reading stabilizes (initial reading may be high or low)
- Pass If: Reading stable within 30 minutes
TEST 2: Fresh Air Test
- Do: Hold sensor near outside air intake or open window
- Expect: Reading drops to ~400-500 PPM (outdoor air level)
- Pass If: Reading drops and stabilizes at outdoor level
TEST 3: Breath Test (Occupancy Simulation)
- Do: Exhale breath directly at sensor from 6-12 inches away for 10 seconds
- Expect: Reading increases 200-400 PPM within 30-60 seconds
- Pass If: Reading increases then gradually returns to baseline
TEST 4: Range Test
- Do: Compare occupied space reading to unoccupied/ventilated reading
- Expect:
- Unoccupied with ventilation: 400-600 PPM
- Occupied space: 600-1200 PPM depending on density
- Pass If: Readings make sense for conditions
TEST 5: Controller Integration
- Sensor appears in controller AI list
- Reading displays in PPM
- Graphics show live data
- Controller uses reading for DCV control
- No faults or errors
TROUBLESHOOTING
NO READING / SENSOR FAULT
- Verify supply voltage at sensor: 24VAC/VDC ±10%
- Wait 30 minutes for warm-up period
- Check all wiring connections tight
- Test continuity end-to-end: <5 ohms
- Measure output signal: Should be 2-10V or 4-20mA (not 0V or 0mA)
- If 0V or 0mA: Sensor failed - replace
- If voltage present but no reading: Check controller input config
READING STUCK / NOT CHANGING
- Verify sensor has power (LED indicator if equipped)
- Wait for warm-up period (30 min)
- Perform breath test - should increase reading
- Check sensor lens/opening not obstructed or dirty
- If still stuck: Replace sensor (NDIR element failed)
READING TOO HIGH (Always >1000 PPM)
- Check sensor location:
- Near kitchen or break room?
- In dead air space with poor circulation?
- Too close to occupants?
- Verify outdoor air ventilation operating correctly
- Compare to portable CO2 meter (calibrated reference)
- If consistently high by same offset: Calibrate sensor
- If true high reading: Increase ventilation rate
READING TOO LOW (Always <400 PPM)
- Check sensor location - too close to OA intake or supply diffuser?
- Verify sensor not in high-velocity airstream
- Compare to portable CO2 meter
- If sensor reads low: Calibrate or replace
- Note: Reading below 400 PPM indoors is usually sensor error
ERRATIC / FLUCTUATING READINGS
- Check for air currents affecting sensor (supply diffuser too close)
- Verify sensor mounted securely (not vibrating)
- Check wiring for EMI/RFI interference
- Look for moisture in sensor or connections
- If persists: Replace sensor
SLOW RESPONSE
- Normal: CO2 sensors respond slower than temperature (1-2 min typical)
- Check sensor sampling rate (some have adjustable averaging)
- Verify sensor not obstructed
- If >5 minutes to respond: Sensor may be failing - replace
ESCALATION - COMPLETE BEFORE CALLING
PRE-ESCALATION CHECKLIST
- Verified supply voltage at sensor (24V ±10%)
- Waited 30+ minutes for warm-up period
- Verified all wiring connections
- Performed breath test (reading should increase)
- Compared to portable CO2 meter (if available)
- Checked sensor location (away from influences)
- Documented readings over 30+ minute period
- Taken photos of installation and location
PROVIDE THIS INFO
- Sensor: [Mfg / Model / Range / Location]
- Supply Voltage: _____ VAC/VDC
- Output Signal: 0-10V or 4-20mA
- Current Reading: _____ PPM
- Reference Reading: _____ PPM (if available)
- Space Occupancy: Occupied / Unoccupied / # people
- Ventilation Status: OA damper position ____ %
- Symptoms: [Stuck, erratic, high, low, no reading]
- Response to Breath Test: [Increased / No change]
- Steps Taken: [Troubleshooting completed]
CONTACTS
- Field Specialist: [Phone]
- Programmer: [Phone] (if DCV sequence issue)
- Project Manager: [Phone]
- Dispatch: [Phone]
CALIBRATION
When Needed:
- Annual calibration recommended (NDIR sensors drift over time)
- After sensor replacement
- If reading consistently off by >100 PPM
Methods:
OPTION A: Fresh Air Calibration (Simple)
- Expose sensor to outdoor air for 20+ minutes
- Outdoor air should read 400-450 PPM
- Adjust sensor calibration to 400 PPM (if adjustable)
- Note: Only accurate if outdoor air is actually ~400 PPM
OPTION B: Zero Gas Calibration (Accurate)
- Requires calibration gas (400 PPM CO2 in nitrogen)
- Apply calibration gas to sensor per manufacturer procedure
- Adjust sensor to match calibration gas concentration
- Preferred method - most accurate
OPTION C: Controller Offset (Temporary)
- If sensor consistently off by fixed amount (e.g., always reads 100 PPM high)
- Apply offset in controller configuration
- Not a permanent fix - sensor should be recalibrated or replaced
Acceptable Tolerance: ±50 PPM
Document: Tech name, date, calibration method, before/after readings
COMMON ISSUES & TIPS
✓ Mount height: 4-6 feet (breathing zone) - CO2 heavier than air but well-mixed indoors
✓ Warm-up time: Always allow 30 min minimum after power-up before commissioning
✓ Location critical: Representative location essential - avoid OA intakes and supply diffusers
✓ NDIR technology: Most accurate but requires annual calibration
✓ Range selection: 0-2000 PPM for most spaces, 0-5000 PPM for high-occupancy (auditoriums, gyms)
✓ DCV savings: Typically 10-30% energy savings vs fixed ventilation rate
✓ ASHRAE 62.1: Requires CO2 sensors for DCV in densely occupied spaces
✓ Breath test: Quick field verification - exhaled breath ~40,000 PPM CO2
✓ Outdoor air: ~400-450 PPM baseline (slowly increasing globally ~2 PPM/year)
✓ False high readings: Check for nearby combustion sources, kitchens, smoking
✓ Multi-zone systems: One sensor per zone typical, or duct-mounted in return air
Document ID: SSO-CO2-001
Revision: 1.0
Next Review: Dec 2026